Inspection
Inspection Details
Equipment ID
907
907
Inspection Date
6/7/2021
6/7/2021
Inspection Type
Special Inspection
Special Inspection
Inspector Name
Michael Terhune
Michael Terhune
Mechanic Name
Joseph Ammons
Joseph Ammons
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
44a3541e-dd44-4ac9-93d5-8cf9264bd701
44a3541e-dd44-4ac9-93d5-8cf9264bd701
Location
Broadway Bldg
221 W HIGH ST, JEFFERSON CITY, MO
Phone: (573) 751-4287
221 W HIGH ST, JEFFERSON CITY, MO
Phone: (573) 751-4287
Owner
Attn: INTERAGENCY
State of MO- Broadway Bldg-INTERAGENCY
221 W HIGH ST, JEFFERSON CITY, MO 65101
Phone: (000) 000-0000
State of MO- Broadway Bldg-INTERAGENCY
221 W HIGH ST, JEFFERSON CITY, MO 65101
Phone: (000) 000-0000
Billing
Attn: INTERAGECNY
OA-FMDC- HST RM 730-INTERAGECNY
PO BOX 809, JEFFERSON CITY, MO 65102
Phone: (000) 000-0000
OA-FMDC- HST RM 730-INTERAGECNY
PO BOX 809, JEFFERSON CITY, MO 65102
Phone: (000) 000-0000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Main hoist ropes rouged and undersized. | 1/27/2020 | |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | x | Main hoisting ropes rouged, and undersized. | 2/1/2021 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Emergency phone working, but not identifying location. | 2/1/2022 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate in machine room. | 2/29/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | x | 6th floor landing door has worn gib. | 2/1/2022 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | Provide FFS testing log in machine room. | 2/29/2024 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.2.7 | x | Emergency power not tested at time of inspection. | 2/1/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | Provide type ABC fire extinguisher in machine room. | 2/29/2024 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Provide MCP in machine room. | 2/29/2024 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate in machine room. | 2/29/2024 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone not working. | 2/9/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.2.7 | x | Standby power not tested at time of inspection. | 2/9/2023 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Provide an up to date fire extinguisher in machine room. | 2/29/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Provide an MCP in machiner room. | 2/29/2024 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current operating certificate in machine room. | 2/29/2024 | ||
| MO Minimum : Elevators | (J) - Counterweights | (J)2 | Counterweight rollers worn, replace. | 5/20/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | x | Floor 4 landing door missing one gib. | 7/15/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Car selector on cartop needs new guides. | 5/20/2024 |