Inspection
Inspection Details
Equipment ID
12771
12771
Inspection Date
6/4/2021
6/4/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
a2483d51-cce3-4e38-9a9b-cb23c9124da7
a2483d51-cce3-4e38-9a9b-cb23c9124da7
Location
Wire Works Lofts
1445 S 18th St, St. Louis, MO
Phone: (314) 776-6000
1445 S 18th St, St. Louis, MO
Phone: (314) 776-6000
Owner
Attn: Sue Lewis
Wire Works in the Square LP
1445 S 18TH ST, SAINT LOUIS, MO 63104
Phone: (314) 776-6000
Wire Works in the Square LP
1445 S 18TH ST, SAINT LOUIS, MO 63104
Phone: (314) 776-6000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | x | Phone volume is way too low in cab. Repair. | 2/6/2019 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Emergency phone shall work. | 2/17/2021 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 6/4/2021 | |
| A17.1-1996 : Elevators | 3.17 - Door and gate equipment | 1001.2(c)(23) | Replace the missing top floor pick up rollers. | 1/9/2023 | ||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | The pit lighting shall be operational. | 1/9/2023 | ||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | The pit shall be kept clean. Clean the pit. | 1/9/2023 | ||
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. (Currently no dial tone) | 7/29/2021 | |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | This elevator is equipped with an unsealed overspeed valve. A category 5 test shall be performed on the overspeed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 1/9/2023 | ||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | The pit shall be kept clean. Remove excess debris. | 11/8/2023 | ||
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Battery lowering shall work. Take corrective action as needed. | 12/11/2023 | |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | There are no lights in the machine room. Provide code compliant lighting. |