Inspection
Inspection Details
Equipment ID
15700
15700
Inspection Date
8/24/2017
8/24/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
John Ryan
John Ryan
Mechanic Name
Relief Valve Pressure
530
530
Slide
Governor Rope Pull
Door Closing Force
29
29
External ID
Location
Harris Stowe Early Childhood Development
10 N Compton, St. Louis, MO
Phone: (314) 340-3366
10 N Compton, St. Louis, MO
Phone: (314) 340-3366
Owner
Harris Stowe Early Childhood Development
3026 Laclede Ave, St. Louis, MO 63103
3026 Laclede Ave, St. Louis, MO 63103
Billing
Attn: Harris Stowe Early Childhood Development
3026 Laclede Ave, , MO 63103
3026 Laclede Ave, , MO 63103
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Existing cab emergency telephone doe not work and shall be repaired and tested. | 7/20/2018 |
| conversion | conversion | n/a | No | No | Phase 1 key station has a broken jewel bezel on the fireman's hat indicator, said jewel shall be replaced. | 11/17/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.1.4(l) | Yes | Yes | Firemans Phase 1 bezel is missing and shall be replaced. | 11/17/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/11/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve. Based on the installation date of 2008, the overspeed valve is due for a category 5 test on or before the next annual inspection. | 9/11/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | This elevator is equipped with an unsealed overspeed valve. A category 5 test shall be performed and witnessed within 90 days. | 9/11/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/11/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Fire extinguisher is expired. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Mo State operating certificate is expired. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.3 - Operating control devices | 2.26.1.1 | No | No | Second floor button is broken and shall be repaired or replaced. |