Inspection
Inspection Details
Equipment ID
8886
8886
Inspection Date
6/3/2021
6/3/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Todd Davis
Todd Davis
Relief Valve Pressure
560
560
Slide
Governor Rope Pull
Door Closing Force
15
15
External ID
8d8d487e-c492-4583-8ce7-547de8e9f096
8d8d487e-c492-4583-8ce7-547de8e9f096
Location
U-Haul- O'Fallon
2000 Hwy K, O'Fallon, MO
Phone: (636) 980-9111
2000 Hwy K, O'Fallon, MO
Phone: (636) 980-9111
Owner
Attn: U-Haul- International
U-Haul- International
PO Box 21502, Phoenix, AZ 85036
Phone: (000) 000-0000
U-Haul- International
PO Box 21502, Phoenix, AZ 85036
Phone: (000) 000-0000
Billing
Attn: U-Haul Company of St. Louis
UHaul Co of Missouri NE
12060 Lusher Rd, St. Louis, MO 63138
Phone: (314) 355-7920
Email: tammy-wittman@uhaul.com
UHaul Co of Missouri NE
12060 Lusher Rd, St. Louis, MO 63138
Phone: (314) 355-7920
Email: tammy-wittman@uhaul.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Red Tag) | Yes | No | In cab emergency telephone does not work, and shall be repaired and retested. | 6/12/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency telephone shall work. | 7/8/2019 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 7/1/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Security company monitoring elevator cab phone could not give the location of elevator. Program or repair phone to provide location. Re-inspection required | 11/9/2022 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | Yes | No | Teh emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspect by 7/13/23 (30 days) | 8/2/2023 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency lighting shall work. Multi-year violaton. | 9/18/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm Bell shall work with loss of main 120v power. | 9/18/2024 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | No | No | Non-elevator related items shall not be stored in the machine room. | 9/30/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Fire service testing must be documented monthly. | 9/30/2024 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1206.2b (Clean Machine Room) | No | No | Non-elevator related items shall not be stored in the machine room. | 9/30/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Fire service testing must be documented monthly. Note: Last documented test was the June 2024 annual inspection. | 9/30/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Fire service testing must be documented monthly | 7/16/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Car lighting disconnect in machine room requires a proprietary key which was not found in the room. Provide key to be left in machine room. | 7/16/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/16/2025 |