Inspection
Inspection Details
Equipment ID
12248
12248
Inspection Date
6/9/2021
6/9/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Paul Stuhlsatz
Paul Stuhlsatz
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
3c5386c0-f6b1-405e-8256-6bdc3c8190ed
3c5386c0-f6b1-405e-8256-6bdc3c8190ed
Location
St. Louis University Hospital
3635 Vista Ave at Grand, St. Louis, MO
Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
3635 Vista Ave at Grand, St. Louis, MO
Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
Owner
Attn: Janet Dickson
SSM Saint Louis University Hospital
3635 Vista Ave at Grand, St. Louis, MO 63110
Phone: (314) 989-6134
Alt Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
SSM Saint Louis University Hospital
3635 Vista Ave at Grand, St. Louis, MO 63110
Phone: (314) 989-6134
Alt Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | both bottom and top demarcation lights not working | 2/7/2020 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(E) | No | No | Replaced comb plates with missing teeth. | 2/7/2020 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | Yes | Yes | Step has broken riser. 3 steps have broken fin on step treads. Red tagged until repaired. | 8/4/2022 |
| Missouri Minimum : Escalators | 11 CSR 40-5.090 Inspection and Testing | 8.6.11.6.1(b)(Not accessible to public) | No | No | The escalator has been placed out of service and is being used as a means of egress. The escalator shall be either returned to service or properly barricaded to prevent the public from using the escalator as a stairway. | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | There shall be maintenance records kept in the escalator machine space accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.2 Escalator Step-to-Skirt Clearance | Yes | No | The step/skirt index is at too great of a gap and coefficient. Adjust step/skirt index to be under the maximum limits. | 6/10/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unable to perform testing of brake torque and step indexing due to tool failure. Need to perform both tests to complete inspection. Re-inspection required | 8/6/2025 |
| Missouri Minimum : Escalators | 11 CSR 40-5.090 Inspection and Testing | 8.6.11.6.1(b)(Not accessible to public) | No | No | The escalator has been placed out of service and is being used as a means of egress. The escalator shall be either returned to service or properly barricaded to prevent the public from using the escalator as a stairway. | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | There shall be maintenance records kept in the escalator machine space accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.2 Escalator Step-to-Skirt Clearance | Yes | No | The step/skirt index is at too great of a gap and coefficient. Adjust step/skirt index to be under the maximum limits. | 8/6/2025 |
| Missouri Minimum : Escalators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | Yes | Step/Skirt index at too great of a gap. Adjust step/skirt index to be under the maximum limit. Unit red tagged. | |
| Missouri Minimum : Escalators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(b)(3) Escalators Placed out of Service | Yes | Yes | The escalator has been placed out of service and is being used as a means of egress. The escalator shall be either returned to service or properly barricaded to prevent the public from using the escalator as a stairway. | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | There shall be maintenance records kept in the escalator machine space accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. |