Inspection
Inspection Details
Equipment ID
12250
12250
Inspection Date
6/11/2021
6/11/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Paul Stuhlsatz
Paul Stuhlsatz
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
5534185a-5148-4f36-9d9c-28d23f6db6ba
5534185a-5148-4f36-9d9c-28d23f6db6ba
Location
St. Louis University Hospital
3635 Vista Ave at Grand, St. Louis, MO
Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
3635 Vista Ave at Grand, St. Louis, MO
Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
Owner
Attn: Janet Dickson
SSM Saint Louis University Hospital
3635 Vista Ave at Grand, St. Louis, MO 63110
Phone: (314) 989-6134
Alt Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
SSM Saint Louis University Hospital
3635 Vista Ave at Grand, St. Louis, MO 63110
Phone: (314) 989-6134
Alt Phone: (314) 577-8072
Email: Janet.Dickson@ssmhealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| Missouri Minimum : Escalators | 11 CSR 40-5.090 Inspection and Testing | 8.6.11.6.1(b)(Not accessible to public) | No | No | The escalator has been placed out of service and is being used as a means of egress. The escalator shall be either returned to service or properly barricaded to prevent the public from using the escalator as a stairway. | 5/7/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | There shall be maintenance records kept in the escalator machine space accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. | 5/7/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Escalator malfunctioned and quit running during test. Need to perform the following tests to complete inspection: test drive machine brake torque, stop switches in machine space, all upthrust devices, test all skirt switches, step chain carriage switches, perform step indexing test & test handrail inlet switches. Re-inspection required | 8/7/2025 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | Yes | No | Replace steps witch broken treads. Re-inspection required | 8/7/2025 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | Provide maintenance control program and current maintenance records | 5/7/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Clean escalator truss and machine space | 5/7/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | There shall be maintenance records kept in the escalator machine space accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. This shall be in accordance to the requirements in the Maintenance Control Program. | 5/7/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | Yes | No | Replace steps witch broken treads. Re-inspection required | 5/7/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Clean escalator truss and machine space. | 5/7/2026 |
| A17.1-2016 : Elevators | 7.9 - Steps and upthrust device | 8.6.8.15.9 | Yes | Yes | Lower landing left side upthrust device is broken and will not actuate switch as designed. Red-tagged and removed from service. Re-inspection required | |
| A17.1-2016 : Elevators | 7.17 - Step/skirt clearances, panels, and performance index | 8.6.8.3.3 | Yes | No | Need to perform step indexing test. Re-inspection required | |
| A17.1-2016 : Elevators | 8.12 - Steps, step chains, and trusses | 8.6.8.15.12 | Yes | Yes | Step chains are stretched and worn out creating excessive gap at top landing (1/4") Replace step chains. Red-tagged, removed from service. Re-inspection required | |
| A17.1-2016 : Elevators | 7.19 - Maintenance records | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | Provide up-to-date wiring diagrams | |
| Missouri Minimum : Escalators | 11 CSR 40-5.090 Inspection and Testing | 8.6.11.6.1(b)(Not accessible to public) | No | No | The escalator has been placed out of service and is being used as a means of egress. The escalator shall be either returned to service or properly barricaded to prevent the public from using the escalator as a stairway. | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | Yes | No | Replace steps witch broken treads. Re-inspection required | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Clean escalator truss and machine space. |