Inspection
Inspection Details
Equipment ID
14890
14890
Inspection Date
6/11/2021
6/11/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
Slide
6.5"
6.5"
Governor Rope Pull
60/440
60/440
Door Closing Force
NA
NA
External ID
c8612c74-02e3-457e-a6b7-1da85a22c20f
c8612c74-02e3-457e-a6b7-1da85a22c20f
Location
City View Apts-Bldg 30
110 N 17th St, Bldg 30, St. Louis, MO
Phone: (314) 588-1177
110 N 17th St, Bldg 30, St. Louis, MO
Phone: (314) 588-1177
Owner
Attn: Mills Properties Inc Cityview Apartments
Mills Properties Inc Cityview Apartments
110 N 17TH ST, SAINT LOUIS, MO 63103
Phone: (314) 588-1177
Email: cityviewmanager@millsproperties.net
Mills Properties Inc Cityview Apartments
110 N 17TH ST, SAINT LOUIS, MO 63103
Phone: (314) 588-1177
Email: cityviewmanager@millsproperties.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.20 - Governor rope | 2.18.5 | No | No | 2.18.5.3 - A governor rope data tag shall be installed. | 5/27/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | No | No | 2.20.2.2 - A suspension rope data tag shall be installed. | 1/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | Yes | No | 2.11.11.4 - The GAL type A hall door hanger safety retainers shall be installed according to manufacturers specifications. | 9/15/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc)(3) Replace when diameter is reduced (Re-Inspection) | Yes | No | The hoist ropes are bad and shall be replaced ASAP. Other unit in building was red tagged. Allowing 60 days to replace ropes since other unit is red tagged. | 6/11/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 1/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | Unable to complete the category 5 portion of the test. A category 5 test shall be completed. Category 1 items were completed. | 6/11/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.18.7 | No | No | Hoist ropes shall have data tags installed. | 1/27/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.1(h) Call Cancel Button (Re-Inspection) | Yes | No | Call cancel button on fire service is not working. | 8/27/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. | 8/27/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.3.1(h) Call Cancel Button (Re-Inspection) | Yes | No | Call cancel button on fire service is not working. (Violation not checked during phone re-inspect on 8/27/24) | 2/20/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/27/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door lock is broken and must be repaired to prevent access to machine room by unauthorized persons. Access doors shall be self-closing and self-locking. | 1/27/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | A permanent and unobstructed means of access shall be provided to machine room. | 1/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 1/27/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Phase II fire service, call cancel button not functioning. (2nd Notice) | 1/27/2026 |