Inspection
Inspection Details
Equipment ID
7778
7778
Inspection Date
7/9/2018
7/9/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Jeffrey Carpenter
Jeffrey Carpenter
Relief Valve Pressure
440
440
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
76540a9a-70b7-4324-83cb-728fab137f14
76540a9a-70b7-4324-83cb-728fab137f14
Location
Holt High School
600 CAMPUS DR, WENTZVILLE, MO
600 CAMPUS DR, WENTZVILLE, MO
Owner
Wentzville R-IV School District
1 CAMPUS DR, WENTZVILLE, MO 63385-3415
1 CAMPUS DR, WENTZVILLE, MO 63385-3415
Billing
Attn: Wentzville R-IV School District
1 CAMPUS DR, WENTZVILLE, MO 63385-3415
1 CAMPUS DR, WENTZVILLE, MO 63385-3415
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (E) - Machines | (E)1 | No | No | Low pressure switch on control valve does not work. Repair and Reinspect within 30 days. 2.37 | 1/3/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light needs to be repaired. | 10/9/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work when normal power is removed. Reprogram phone to new maintenance company | 7/19/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | A written maintenance control program shall be kept on site for each elevator | 7/19/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Unit has oil recovery pump in pit. Replace with proper receptacle to measure oil leakage from jack | 7/19/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current certificate. | 8/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Remove scavenger unit from the pit. | 8/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Provide code compliant means to collect oil from piston in the pit. | 8/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide current year documents for the MCP. | 8/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Unit has oil recovery pump in pit. Replace with proper receptacle to measure oil leakage from jack | 8/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Packing on piston shall be replaced, excessive leaking | 8/12/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication is not working. Re-inspection required | 6/24/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Packing on piston needs replaced, excessive leaking | 8/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Unit has oil recovery pump in pit. Replace with proper receptacle to measure oil leakage from jack | 8/12/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to remove scavenger unit from pit | 8/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Provide code compliant means to collect oil from the piston | 8/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | Packing on piston needs replaced, excessive leaking. Re-inspection required | 8/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Unit has oil recovery pump in pit. Need to replace with proper receptacle to measure oil leakage from jack | 8/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Need to remove scavenger unit from pit | 8/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Re-inspection required |