Inspection
Inspection Details
Equipment ID
11779
11779
Inspection Date
6/15/2021
6/15/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Elder
Michael Elder
Mechanic Name
Ralph Kinnison
Ralph Kinnison
Relief Valve Pressure
375
375
Slide
Governor Rope Pull
Door Closing Force
N/A
N/A
External ID
b968fe09-2d68-4e32-813a-78b6df42f7c9
b968fe09-2d68-4e32-813a-78b6df42f7c9
Location
Con Agra Frozen Foods
200 N Banquet Dr, Marshall, MO
Phone: (660) 236-6107
Email: SCOTTIE.MCKENZIE@CONAGRAFOODS.COM
200 N Banquet Dr, Marshall, MO
Phone: (660) 236-6107
Email: SCOTTIE.MCKENZIE@CONAGRAFOODS.COM
Owner
Attn: Con Agra Frozen Foods
Con Agra Frozen Foods
200 N Banquet Dr, Marshall, MO 65340
Phone: (660) 236-6065
Email: SCOTTIE.MCKENZIE@CONAGRAFOODS.COM
Con Agra Frozen Foods
200 N Banquet Dr, Marshall, MO 65340
Phone: (660) 236-6065
Email: SCOTTIE.MCKENZIE@CONAGRAFOODS.COM
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (A) - Hoistways | (A)10 | No | No | No easy access to pit | 8/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency phone not working | 1/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working | 8/12/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit full of trash. Pieces of broken pallets. | 8/1/2022 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)6 | No | No | missing capacity plate in car | 5/15/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)7 | No | No | repair pit stop switch | 5/15/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | lots of broken pallet debris on pit floor clean same | 5/15/2026 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | Yes | No | stop sw in cab knocked inside of car station. remount and test | 5/15/2026 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)6 | No | No | Provide capacity plate in car. | 6/1/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)7 | Yes | Yes | Pit switch broken. | 6/1/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | Yes | Debris in pit, remove. | 6/1/2026 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)1 | Yes | Yes | In car stop switch broken. | 6/1/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | Yes | Yes | Both landing door guides and related devices aged and badly worn. Repair as necessary. | 6/1/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | Yes | Yes | Hoistway landing door vision panels damaged/missing. | 6/1/2026 |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)6 | Yes | Yes | Guide shoe liner missing, causing severe damage to shoe frame. | 6/1/2026 |
| MO Minimum : Elevators | (N) - Guide Rails | (N)2 | Yes | Yes | Guide rail SEVERELY worn from missing guide shoe. Unit removed from service. | 6/1/2026 |