Inspection
Inspection Details
Equipment ID
13227
13227
Inspection Date
6/15/2021
6/15/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Elder
Michael Elder
Mechanic Name
Ralph Kinnison
Ralph Kinnison
Relief Valve Pressure
550
550
Slide
Governor Rope Pull
Door Closing Force
210
210
External ID
3115441e-a168-400d-8d95-d1b4cafc48e2
3115441e-a168-400d-8d95-d1b4cafc48e2
Location
Con Agra Frozen Foods
200 N Banquet Dr, Marshall, MO
Phone: (660) 236-6107
Email: SCOTTIE.MCKENZIE@CONAGRAFOODS.COM
200 N Banquet Dr, Marshall, MO
Phone: (660) 236-6107
Email: SCOTTIE.MCKENZIE@CONAGRAFOODS.COM
Owner
Attn: Con Agra Frozen Foods
Con Agra Frozen Foods
200 N Banquet Dr, Marshall, MO 65340
Phone: (660) 236-6065
Email: SCOTTIE.MCKENZIE@CONAGRAFOODS.COM
Con Agra Frozen Foods
200 N Banquet Dr, Marshall, MO 65340
Phone: (660) 236-6065
Email: SCOTTIE.MCKENZIE@CONAGRAFOODS.COM
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | FS No Audible or Visual Signals on Phase I recall. | 10/12/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Phase II operation not working. | 10/12/2018 |
| A17.1-1996 : Elevators | 4.4 - Hoistway door locking devices | 111 | Yes | Yes | Freight Bi-Parting Landing Door Mechanical lock broken doors could be opened by separating with car away from landing. | 10/17/2018 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | phone not working | 10/18/2020 |
| A17.1-1996 : Elevators | 4.1 - Car platform guard | 203.9 | No | No | toe guard needs to be replaced only covers less than half of opening | 1/1/2023 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | lot of debris in pit 106.2a | 1/1/2023 |
| A17.1-1996 : Elevators | 4.1 - Car platform guard | 203.9 | No | No | needs new platform guard installed | 1/1/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working | 1/5/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working | 5/24/2022 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | Overspeed valve tripping above 140% of down speed. Rusted up so can't adjust | 1/1/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working | 11/16/2022 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | In case of fire don't use elevator signage needed | 1/1/2023 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Phase 2 key switch not working | 11/16/2022 |
| A17.1-2016 : Elevators | 1.2 - Stop Switches | 8.11.2.1.1(b) | No | No | In car stop switch works in up direction but not down. May tie in to phase 2 key switch problem. Used as no rider so left running | 1/23/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Telephone Incoming Line is bad must replace or repair & retest. | 1/6/2023 |