Inspection
Inspection Details
Equipment ID
14767
14767
Inspection Date
7/11/2018
7/11/2018
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Steven Himmelmann
Steven Himmelmann
Relief Valve Pressure
330
330
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
293f89b6-8127-4475-b1b4-f9f79a412f58
293f89b6-8127-4475-b1b4-f9f79a412f58
Location
Oxford Hill Condominiums
10367 OXFORD HILL DR, SAINT LOUIS, MO
10367 OXFORD HILL DR, SAINT LOUIS, MO
Owner
The Manor Condo at Oxford Hill
PO BOX 37106, SAINT LOUIS, MO 63141-1606
PO BOX 37106, SAINT LOUIS, MO 63141-1606
Billing
Attn: Grier Group Management Company
1400 ELBRIDGE PAYNE RD, CHESTERFIELD, MO 63017-8520
1400 ELBRIDGE PAYNE RD, CHESTERFIELD, MO 63017-8520
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | machine room shall be kept clean and dry | 6/12/2026 |
| conversion | conversion | n/a | No | No | No current state operation certificate in elevator machine room. | 6/12/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | No | No | Car Door Restrictor does not work. Repair and Reinspect. 1.18 | 6/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Relocate tape selector mounting bracket on car top. Hits selector tape mounting bracket when doing stop ring pressure test | 6/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Standing water on machine room floor and in front of controller creating electrical hazard | 8/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Car shall have functioning Normal Terminal Limits actuating before Final Terminal Limit. | 8/1/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current Operating Certificate in machine room | 8/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Selector Reader head hits selector tape mounting bracket during stop ring pressure test | 8/1/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.4 Plunger Gripper Testing | No | No | Plunger Gripper due to be tested with rated load recurring every 5 years. | 8/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Phone in car fails to establish two-way communication | 5/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace knocked out Down Hall Call Button at the second landing | 6/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher in the machine room is due to be serviced or replaced | 6/12/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | There is water on the machine room floor. Machine rooms need to be kept clean and dry. | 6/12/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | There is water on the machine room floor. Machine rooms need to be kept clean and dry. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher in the machine room is due to be serviced or replaced |