Inspection
Inspection Details
Equipment ID
17061
17061
Inspection Date
6/1/2021
6/1/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Andrew Schmitz
Andrew Schmitz
Relief Valve Pressure
630
630
Slide
Governor Rope Pull
Door Closing Force
22/20
22/20
External ID
e233ade7-f05e-4306-b0c6-ce56c3431d6b
e233ade7-f05e-4306-b0c6-ce56c3431d6b
Location
Target- St. Louis
4255 Hampton Ave, St. Louis, MO
Phone: (314) 802-0122
4255 Hampton Ave, St. Louis, MO
Phone: (314) 802-0122
Owner
Attn: Tim Fournier/CC-2809
Target Corporation-Target Store T1515
33 S 6th St, Minneapolis, MN 55403
Phone: (000) 000-0000
Email: TargetVT@target.com
Target Corporation-Target Store T1515
33 S 6th St, Minneapolis, MN 55403
Phone: (000) 000-0000
Email: TargetVT@target.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Post Mo State operating permit in machine room | 10/19/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Need testing procedures in MCP on or before 1/1/22 | 5/22/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room Overspeed valve set at 171 | 2/10/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | Yes | No | Front and rear restrictors shall work. | 7/3/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | Machine room fire extinguisher shall be permanently mounted to the wall. | 7/3/2025 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | Yes | No | Lighting disconnect fused improperly. Replace 20A fuse with proper 15A. | 7/3/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | Yes | No | Hall calls shall work. | 7/3/2025 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 Door Systems | Yes | No | Adjust upthrusts for proper clearances (2nd floor front). | 7/3/2025 |
| A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 Door Systems | Yes | No | Adjust upthrusts for proper lower gap opening. | 7/3/2025 |
| A17.1-2016 : Elevators | 4.5 - Access to Hoistway | 8.6.4.14 Hoistway Access Switches | Yes | No | Adjust hoistway access limit (PIT) for proper stopping heights. | 7/3/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | INCOMPLETE: Remaining testing needed is as follows: pump pressures and speed, relief pressure, OSV, rear door torque, phase I & II fire service, FAID and recalls, battery lowering, COP stop, low oil, and 15 min static testing. | 7/3/2025 |