Inspection
Inspection Details
Equipment ID
17749
17749
Inspection Date
6/16/2021
6/16/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
2"
2"
Governor Rope Pull
25/100
25/100
Door Closing Force
18
18
External ID
6b94a086-0c79-4f2a-80d3-895a1b3eb9f1
6b94a086-0c79-4f2a-80d3-895a1b3eb9f1
Location
The Georgian
1515 Lafayette Ave, St. Louis, MO
Phone: (314) 771-7171
1515 Lafayette Ave, St. Louis, MO
Phone: (314) 771-7171
Owner
Attn: The Georgian Condo Association
Sentry Management Inc
9666 Olive Blvd, Ste 116, St. Louis, MO 63132
Phone: (314) 994-7440
Email: jblaha@sentrymgt.com
Sentry Management Inc
9666 Olive Blvd, Ste 116, St. Louis, MO 63132
Phone: (314) 994-7440
Email: jblaha@sentrymgt.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 6/16/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not ring to 24x7 support. | 6/18/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide on-site maintenance control program. | 3/15/2024 |
| A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 1001.2(c)(2) | No | No | Car top outliet has open ground indicated. Repair as needed. | 9/22/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Clean pit and oil from floor. | 9/22/2022 |
| A17.1-1996 : Elevators | 2.17 - Drive machine brake | 1001.2(b)(15) | Yes | Yes | Failed 125% brake test. Car would not stop at floor level, ran into pit. Red tagged unit. | 6/18/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not ring to 24x7 support. | 9/6/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide on-site maintenance records. | 3/15/2024 |
| A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 1001.2(c)(2) | No | No | Car top outlet has open ground indicated. Repair as needed. | 9/22/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Clean pit and oil from floor. | 9/22/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be on display in the machine room | 9/22/2022 |
| A17.1-1996 : Elevators | 3.28 - Counterweight and counterweight buffer | 202 | No | No | Top counterweight guide shoe insert is coming out of holder, causing guide to scrape guide rail, repair / replace same | 9/22/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean oil & debris from pit floor | 9/22/2022 |
| A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 204.7 | No | No | Cartop outlet has open ground indicated, repair as needed | 9/22/2022 |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Room and Machinery Space | No | No | Remove non-elevator related materials from machine room |