Inspection
Inspection Details
Equipment ID
11688
11688
Inspection Date
6/8/2021
6/8/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gregory Sacks
Gregory Sacks
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
24
24
External ID
649d5441-408f-4b6d-a3cc-969879fc359b
649d5441-408f-4b6d-a3cc-969879fc359b
Location
Motor Lofts
2206 Lucas Ave, St. Louis, MO
Phone: (314) 504-3796
2206 Lucas Ave, St. Louis, MO
Phone: (314) 504-3796
Owner
Motor Lofts
416 N 23RD ST, SAINT LOUIS, MO 63103-1547
416 N 23RD ST, SAINT LOUIS, MO 63103-1547
Billing
Attn: Motor Lofts
416 N 23RD ST, SAINT LOUIS, MO 63103-1547
416 N 23RD ST, SAINT LOUIS, MO 63103-1547
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | All phases of fire service shall be tested. | 7/10/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Counterweight buffer shall be tested. | 7/10/2018 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Yes | No | Provide existing pit light to work. | 6/21/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone to work with 24/7 support. | 6/21/2019 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | In cab emergency lighting shall work. | 4/29/2021 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 1001.2(b)(1) | No | No | The machine room shall not be used for storage of non-elevator related items. | 4/29/2021 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | The in car emergency lighting shall be operational. | 4/29/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP shall be provided. Currently missing evacuation plan, fire service testing log, maintenance log, and repair log. | 12/10/2021 |
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 1001.2(a)(12) | No | No | The handrail on the back of the cab is loose. | 12/10/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Could not complete inspection due to difficulty getting unintended motion parameter to hold status. The following items still need be tested: (1) Testing of emergency light, alarm and/or bell with 110V source removed, (2) run and scan of the hoistway, (3) fire service testing, (4) complete category 5 test. | 10/19/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Clean the pit of dirt and debris. | 10/22/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 10/22/2023 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | The lighting at the top of the hoistway for the machinery space does not work. Take corrective action. | 10/22/2023 |