Inspection
Inspection Details
Equipment ID
22918
22918
Inspection Date
6/10/2021
6/10/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
Instantaneous
Instantaneous
Governor Rope Pull
25/200
25/200
Door Closing Force
25
25
External ID
8da16be6-dcf3-45a8-ad65-417e0b151df0
8da16be6-dcf3-45a8-ad65-417e0b151df0
Location
Spectrum Retirement Corporation
2929 DOUGHERTY FERRY RD, SAINT LOUIS, MO
Phone: (636) 825-6665
2929 DOUGHERTY FERRY RD, SAINT LOUIS, MO
Phone: (636) 825-6665
Owner
Attn: S/K Ellisville LLC
S/K Ellisville LLC
200 SPRUCE ST, DENVER, CO 80230
Phone: (000) 000-0000
Email: sstehlick@spectrumretirement.com
S/K Ellisville LLC
200 SPRUCE ST, DENVER, CO 80230
Phone: (000) 000-0000
Email: sstehlick@spectrumretirement.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | x | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 5/24/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Emergency power test was unsuccessful. The elevator shall operate with no load in the car while operating on the emergency generator. | 11/23/2022 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | x | Replace any missing fire tabs on hoistway doors. | 3/19/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Emergency power operation shall be tested. | 3/19/2024 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and related on-site documentation shall be provided in the machine room. The fire service testing log shall be documented monthly. | 3/16/2024 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | MCP Fire service testing must be properly documented monthly on log sheet. | 12/9/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1, with identification of the person(s) that performed the operation and the date shall be available on-site. | 12/9/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 12/9/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Emergency power shall be tested. A test was attempted, but the power did not successfully transfer. | 12/9/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.29.1 | The disconnecting means (both main and car lighting) shall be marked identifying it as belonging to the elevator with a minimum of 2" in height and of contrasting color to its background. There are 4 disconnects in the machinery space and none are marked to identify what device they feed. | 12/9/2025 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Slide, Gov pullout/pull thru, and gov switch/jaw shall be tested. | 12/9/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Still requires up to date operating certificate in the machine room. |