Inspection
Inspection Details
Equipment ID
23053
23053
Inspection Date
6/25/2018
6/25/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
Slide
Governor Rope Pull
n/a
n/a
Door Closing Force
18
18
External ID
f9872a8f-038d-4dbc-a29a-677c05bcb675
f9872a8f-038d-4dbc-a29a-677c05bcb675
Location
Lindell Residences LLC
4653 LINDELL BLVD, SAINT LOUIS, MO
4653 LINDELL BLVD, SAINT LOUIS, MO
Owner
Lindell Residences LLC
4653 LINDELL BLVD, SAINT LOUIS, MO 63108-3701
4653 LINDELL BLVD, SAINT LOUIS, MO 63108-3701
Billing
Attn: Lindell Residences LLC
4653 LINDELL BLVD, SAINT LOUIS, MO 63108-3701
4653 LINDELL BLVD, SAINT LOUIS, MO 63108-3701
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.18 | Yes | No | install test tag on governor showing date of acceptance test. | 1/9/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.18 | Yes | No | governor remote trip does in controller does not work. repair. | 1/9/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean elevator pit. | 5/24/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency evacuation battery pack needs replaced. Re-inspection required | 3/6/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be on display in the machine room | 3/20/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not operable, needs repaired. Re-inspection required | 4/4/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 3/2/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator operation while on emergency generator power operation. Re-inspection required | 4/4/2025 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.9 | No | No | Need to install code data plate with required information | 3/2/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency Power shall be tested. | 3/2/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing of the elevator on emergency power. | |
| A17.1-2016 : Elevators | 4.12 - Standby power selection switch | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing of the elevator emergency power selector switch (fire control room). | |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 2.18.4 | Yes | No | Means (solenoid) to remotely activate governor not working properly. |