Inspection
Inspection Details
Equipment ID
1864
1864
Inspection Date
7/9/2018
7/9/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dennis Parker
Dennis Parker
Mechanic Name
Ken Koppel
Ken Koppel
Relief Valve Pressure
240
240
Slide
Governor Rope Pull
Door Closing Force
30
30
External ID
df0ca8d8-bee7-46fd-beea-da9eaa4ee287
df0ca8d8-bee7-46fd-beea-da9eaa4ee287
Location
Tivoli Building
6358 DELMAR BLVD, UNIVERSITY CITY, MO
6358 DELMAR BLVD, UNIVERSITY CITY, MO
Owner
Edwards, Joe
6504 DELMAR BLVD, UNIVERSITY CITY, MO 63130-4501
6504 DELMAR BLVD, UNIVERSITY CITY, MO 63130-4501
Billing
Attn: Hamsterland LLC
6504 DELMAR BLVD, UNIVERSITY CITY, MO 63130-4501
6504 DELMAR BLVD, UNIVERSITY CITY, MO 63130-4501
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair emergency light and alarm bell. | 10/15/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Machine room shall not be used for storage for items that are not related to the maintenance or operation of the elevator | 3/14/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | Door force exceeds 30#, adjust as needed. | 7/31/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Provide existing phone in car to work. Has 52v. Has no key pad, does not work correctly. | 9/7/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Car failed 15 minute stand test, tech determined it to be leaking back through the valve. Repair as needed, reinspect. | 9/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Provide MCP. | 7/31/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | Yes | No | Car door force exceeds 30#, adjust as needed | 9/7/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in car has power, but doesn't work. Repair or replace. Re-inspection required | 9/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Yes | No | A written copy of the MCP shall be kept in the machine room for each unit | 9/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 11/7/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/7/2025 |