MO Minimum : Elevators
|
(C) - Car Enclosure: Freight
|
(C)5
|
No
|
No
|
1. Bulbs or tubes shall be guarded to prevent breakage. Bulbs are not guarded.
|
9/3/2025
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)1
|
No
|
No
|
2. A permanent, safe, and convenient means of access to machine rooms and machinery spaces must be provided and maintained. Ladder to machine room door has a rung missing and doesn’t provide a safe or convenient means. Ref:2.1.1(a)
|
9/3/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
No
|
No
|
3. Wiring diagrams detailing circuits of all electrical protective devices and critical operating circuits shall be available in the machine room. Wiring diagrams for this unit are not available in machine room. Ref: 8.6.1.6.3
|
9/3/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
No
|
No
|
4. All excess lubricant shall be cleaned from the equipment. Containers used to catch leakage shall not be allowed to overflow. Machines need to be cleaned of excessive lubricants. Ref: 8.6.1.6.2
|
9/3/2025
|
|
MO Minimum : Elevators
|
(K) - Car Platforms and Car Slings
|
(K)5
|
No
|
No
|
5. All elevators with automatic leveling, inching or teasing devices shall have a platform guard or an apron. All other elevators shall have warning chains hung within two inches (2") of the edge of the platform on the entrance sides. Chains shall be of number ten (10) U.S. gauge wire or of equal size. Chains shall extend not less than five feet (5') below the platform and shall not be spaced more than four inches (4") apart. No platform guard.
|
9/3/2025
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)10
|
No
|
No
|
6. Access means shall be provided at one upper landing to permit access to the top of the car, and at the lowest landing if this landing is the normal point of access to the pit. This car has no means of cartop or pit access from the landings.
|
9/3/2025
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
No
|
No
|
7. All pits shall be kept dry, clean and free of equipment or material not relating to the operation of the elevator. The elevator pit has trash in it and needs to be clean.
|
9/3/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
No
|
No
|
Provide on-site maintenance control program.
|
9/3/2025
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency phone is inoperable. Re-inspection required
|
|