Inspection
Inspection Details
Equipment ID
19857
19857
Inspection Date
6/21/2021
6/21/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Scott Breihan
Scott Breihan
Relief Valve Pressure
355
355
Slide
Governor Rope Pull
Door Closing Force
15/17
15/17
External ID
e56caea6-6ab2-43f1-8695-4d491171cac3
e56caea6-6ab2-43f1-8695-4d491171cac3
Location
The Country Club of St. Albans
3165 Saint Albans Rd, St. Albans, MO
Phone: (636) 458-3060
3165 Saint Albans Rd, St. Albans, MO
Phone: (636) 458-3060
Owner
The Country Club of St. Albans
3165 SAINT ALBANS RD, SAINT ALBANS, MO 63073-1203
3165 SAINT ALBANS RD, SAINT ALBANS, MO 63073-1203
Billing
Attn: The Country Club of St. Albans
PO BOX 5, SAINT ALBANS, MO 63073-0005
PO BOX 5, SAINT ALBANS, MO 63073-0005
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Elevator does not close doors on front side and return to phase I | 12/12/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Door hold does not work on front doors on Phase II | 12/12/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Hoistway door at 1st floor missing sight guard. | 5/6/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing sight guard on hoistway door. | 5/6/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Provide on-site maintenance control program. | 5/6/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current certificate | 5/6/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Update log for current year | 5/6/2026 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Failed to open door upon lobby recall. | 7/14/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Unable to check Phase II, failed Phase I. | 7/14/2022 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | Yes | Yes | There are many wire runs unrelated to the elevator in the hoistway which are not enclosed and not properly supported. Some are in the path of the hoistway doors, and in one case, the wire is crossing the face of the elevator guide rail. These shall be removed. Elevator Red Tagged | 7/9/2024 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | Yes | Yes | The wire-way feeding one of the interlocks is broken and the interlock wiring exposed and spliced. This wiring shall be enclosed. Elevator Red Tagged. | 7/9/2024 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Fire service operation shall work as required. Fire service was tested several times and failed in multiple ways such as traveling to incorrect floors, moving in the wrong direction before reversing and arriving at the egress floor, and going into phase two hold operation before recalling on phase one. It failed consistently every time it was tested but was inconsistent in the way it failed. This shall be corrected. Elevator Red Tagged. | 7/9/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/6/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted convenient to the machine room door. | 5/6/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in-car emergency lights shall be operational. | 7/9/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | The means to restrict opening of the front and rear car door shall be operational. | 7/9/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. | 5/6/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in-car emergency lights shall be operational. | 8/15/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | The means to restrict opening of the front and rear car door shall be operational. | 8/15/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | Yes | No | There are many wire runs unrelated to the elevator in the hoistway which are not enclosed and not properly supported. Some are in the path of the hoistway doors, and in one case, the wire is crossing the face of the elevator guide rail. These shall be removed. | 8/15/2025 |