Inspection
Inspection Details
Equipment ID
19858
19858
Inspection Date
6/21/2021
6/21/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Scott Breihan
Scott Breihan
Relief Valve Pressure
425
425
Slide
Governor Rope Pull
Door Closing Force
15
15
External ID
10715702-b15e-478c-bfd0-0d2bdc320685
10715702-b15e-478c-bfd0-0d2bdc320685
Location
The Country Club of St. Albans
3165 Saint Albans Rd, St. Albans, MO
Phone: (636) 458-3060
3165 Saint Albans Rd, St. Albans, MO
Phone: (636) 458-3060
Owner
The Country Club of St. Albans
3165 SAINT ALBANS RD, SAINT ALBANS, MO 63073-1203
3165 SAINT ALBANS RD, SAINT ALBANS, MO 63073-1203
Billing
Attn: The Country Club of St. Albans
PO BOX 5, SAINT ALBANS, MO 63073-0005
PO BOX 5, SAINT ALBANS, MO 63073-0005
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Provide on-site maintenance control program. | 7/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing hoist door sight guard (L) | 7/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Door restrictor needs adjustment. | 7/14/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Update log for current year | 7/16/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 7/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in-car emergency lights shall be operational. | 7/9/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. | 7/16/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | Fire extinguisher is out of date. | 8/15/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.4 | Yes | No | Pit ladder shall be 39" from unlocking device. | 8/15/2025 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | Hoistway penetrations shall be fire sealed (front of HW in the corners between floors) | 8/15/2025 |