Inspection
Inspection Details
Equipment ID
13234
13234
Inspection Date
6/23/2021
6/23/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
25
25
External ID
2f6c0df1-dc1a-4f5c-9b07-97ad82e2b0a0
2f6c0df1-dc1a-4f5c-9b07-97ad82e2b0a0
Location
City Place 1
1 CITYPLACE DR, CREVE COEUR, MO
Phone: (314) 787-1976
1 CITYPLACE DR, CREVE COEUR, MO
Phone: (314) 787-1976
Owner
Attn: RNSI City Place, LLC
RNSI City Place, LLC
2 Cityplace Dr, Ste 460, St. Louis, MO 63141
Phone: (314) 594-5013
Email: cityplace@redico.com
RNSI City Place, LLC
2 Cityplace Dr, Ste 460, St. Louis, MO 63141
Phone: (314) 594-5013
Email: cityplace@redico.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Repair leaking seal on traction machine | 10/8/2025 |
| conversion | conversion | n/a | No | No | Suspension ropes are sliding over traction sheave when performing 125% brake test. Repair within 7 days or unit will be red tagged. | 10/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Unable to test the emergency car lighting and signaling devices. The 110V disconnect for those systems could not be located. Locate and label the disconnect so the emergency systems can be tested properly. | 6/22/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be on display in the machine room | 10/8/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work, needs repair. Re-inspection required | 6/7/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state certificate shall be displayed in the machine room | 10/8/2025 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | Yes | Yes | Top final limit swtch is not actuated before counterweights compress buffer, tractions car. Need to shorten hoist ropes. Red-tagged, Re-inspection required | 7/31/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Selector cable on car side (by hoist motor) has breaks, needs to be replaced | 10/8/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit has standing water. Repair or replace sump pump. Remove rust from pit equipment and apply rust inhibitor to prevent further rust damage | 10/8/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 10/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Selector cable on car side (by hoist motor) has breaks, needs to be replaced | 10/8/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Place current state operating certificate in elevator machine room | 10/8/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fireman's Emergency Service Phase I does not work as designed. This is the only elevator that accesses the bottom garage level. Needs repaired. Re-inspection required | 10/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not answered, needs repaired. Re-inspection required | 10/8/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 10/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not answered, needs repaired. Re-inspection required |