|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
10/27/2021
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test.
|
10/27/2021
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
10/27/2021
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4
|
x
|
|
Where an additional power source is connected to the load side of the disconnecting means, the disconnecting means required in Section 620-51 shall be provided with an auxiliary contact that is positively opened mechanically and the opening shall not be solely dependent on springs. This contact shall cause the additional power source to be disconnected from its load when the disconnecting means is in the open position. Note: When the main disconnect is in the open position, the controller is still being powered by the UPS, which is there for emergency lowering. The auxiliary contact required by 620.91(c) is present and working, but merely feeds an input on the controller. This is the way it was designed by Virginia Controls. It presents a hazard to personnel servicing any electrical device in the control system.
|
12/9/2022
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
8/11/2023
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4
|
x
|
|
Where an additional power source is connected to the load side of the disconnecting means, the disconnecting means required in Section 620-51 shall be provided with an auxiliary contact that is positively opened mechanically and the opening shall not be solely dependent on springs. This contact shall cause the additional power source to be disconnected from its load when the disconnecting means is in the open position. Note: When the main disconnect is in the open position, the controller is still being powered by the UPS, which is there for emergency lowering. The auxiliary contact required by 620.91(c) is present and working, but merely feeds an input on the controller. This is the way it was designed by Virginia Controls. It presents a hazard to personnel servicing any electrical device in the control system. (2nd Notice)
|
8/11/2023
|