Inspection
Inspection Details
Equipment ID
19532
19532
Inspection Date
6/30/2021
6/30/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
17
17
External ID
cab521c7-af89-4b2e-bdc6-812359e3a695
cab521c7-af89-4b2e-bdc6-812359e3a695
Location
The Crescent
153 Carondelet Plz, Clayton, MO
Phone: (314) 727-3900
Email: Jvanmier@thecrescentcondo.com
153 Carondelet Plz, Clayton, MO
Phone: (314) 727-3900
Email: Jvanmier@thecrescentcondo.com
Owner
The Crescent Condominium
155 CARONDELET PLZ STE 100, CLAYTON, MO 63105-3479
155 CARONDELET PLZ STE 100, CLAYTON, MO 63105-3479
Billing
Attn: The Crescent Condominium C/O Community Property Mgmt
242 OLD SULPHUR SPRING RD, MANCHESTER, MO 63021-5353
242 OLD SULPHUR SPRING RD, MANCHESTER, MO 63021-5353
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 4.5 - Access to Hoistway | 1001.2(d)(5) | No | No | The hoistway door access key switch plate on the bottom landing is broken and shall be repaired to operate as designed. | 8/10/2020 |
| A17.1-1996 : Elevators | 4.5 - Access to Hoistway | 1001.2(d)(5) | No | No | The hoistway door access key switch plate on the bottom landing is broken and shall be repaired to operate as designed. | 8/10/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)12 | Yes | No | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: Phase II did not initiate when the fireman's emergency service key was turned to the “ON” position. Reinspection is required. | 4/27/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)12 | Yes | Yes | The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: Phase II did not initiate when the fireman's emergency service key was turned to the “ON” position. The unit is locked out of service until it is repaired and a reinspection has been performed. | 5/1/2020 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide on-site maintenance control program. | |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Clean pit. | |
| A17.1-1996 : Elevators | 3.2 - Car top light and outlet | 1001.2(c)(2) | No | No | Car top outliet has neutral reversed. Repair as needed. | |
| A17.1-1996 : Elevators | 2.17 - Drive machine brake | 1001.2(b)(15) | Yes | Yes | Car does not have emergency brake cable system. Provide and retest. | 7/5/2022 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 1001.2(b)(4) | No | No | Top of hoistway stop switch missing cover. | |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Replace or service fire extinguisher in control room. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Category 5 testing needs to be completed, was only able to conduct annual portion of test. | 7/21/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room |