Inspection
Inspection Details
Equipment ID
5625
5625
Inspection Date
7/3/2018
7/3/2018
Inspection Type
Reinspection
Reinspection
Inspector Name
Derek Rankin
Derek Rankin
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
03a35caa-e7ff-4732-9c1b-5a572ddac40f
03a35caa-e7ff-4732-9c1b-5a572ddac40f
Location
Sunrise Assisted Living
1880 CLARKSON RD, CHESTERFIELD, MO
1880 CLARKSON RD, CHESTERFIELD, MO
Owner
Sunrise Assisted Living
1880 CLARKSON RD, CHESTERFIELD, MO 63017-5000
1880 CLARKSON RD, CHESTERFIELD, MO 63017-5000
Billing
Attn: Sunrise Assisted Living
1880 CLARKSON RD, CHESTERFIELD, MO 63017-5000
1880 CLARKSON RD, CHESTERFIELD, MO 63017-5000
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Door will not stay open on Phase II operation | 7/11/2018 |
| conversion | conversion | n/a | No | No | Repair door Restrictor | 7/11/2018 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is not sealed. Perform OSV test on or before next annual inspection. | 6/22/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work properly. Agent said it sounded "extremely faint" and inspector had to repeat everything multiple times to be understood. | 1/17/2025 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Car door restrictor shall work at all floors. There are parts missing. | 1/17/2025 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | Machine room lighting needs to be repaired. One or more bulbs are not working. | 1/4/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | Fire service testing must be documented monthly. | 1/4/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/4/2025 |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | Yes | No | Elevator car door restrictor does not work, parts are missing, need to repair car door restrictor. Re-inspection required | 7/17/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is inoperable. Re-inspection required | |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Emergency battery lowering is not operational. Re-inspection required |