Inspection
Inspection Details
Equipment ID
22605
22605
Inspection Date
6/24/2021
6/24/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Gregory Sacks
Gregory Sacks
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
b444a8ae-968c-49ae-b05f-0bb0c97a024c
b444a8ae-968c-49ae-b05f-0bb0c97a024c
Location
Children's Specialty Care Center
13001 N Outer 40, St. Louis, MO
Phone: (314) 575-1691
13001 N Outer 40, St. Louis, MO
Phone: (314) 575-1691
Owner
Attn: Jennifer Thompson
BJC Healthcare c/o Cushman & Wakefield
8300 Eager Rd, Ste 600D, St. Louis, MO 63144
Phone: (314) 996-5346
Email: jennifer.l.thompson@cushwake.com
BJC Healthcare c/o Cushman & Wakefield
8300 Eager Rd, Ste 600D, St. Louis, MO 63144
Phone: (314) 996-5346
Email: jennifer.l.thompson@cushwake.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Oil usage, findings for firefighters' service operation tests, and other records, along with instructions for location such records shall be posted. | 6/10/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 3/11/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Emergency/standby power operation of the elevator shall be tested to complete the annual inspection. (Unable to transfer power on date of inspection) | 6/24/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 3/14/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | The fire service testing log is not being filled out. | 3/14/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/14/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency power shall be tested. | 6/1/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | The car door shall be restricted from opening when in the closed position anywhere outside the unlocking zone. | 6/1/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | Yes | No | The unit is equipped with emergency power, but the indicator jewel is not working. | 7/5/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | The car door shall be restricted from opening when in the closed position anywhere outside the unlocking zone. | 7/5/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | The emergency/standby power shall be tested. Emergency power is scheduled to be tested this evening. | 6/5/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | The presence of an overspeed valve has been confirmed, along with an installation date of 2015. The overspeed valve shall be scheduled for the category 5 test on or before the next annual inspection. | 6/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Replace missing upper secondary door retainers on hanger bracket on 3rd floor fast door. | 9/2/2025 |