Inspection
Inspection Details
Equipment ID
19912
19912
Inspection Date
5/11/2021
5/11/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Daniel Novak
Daniel Novak
Relief Valve Pressure
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
10
10
External ID
dce2e586-096e-4b18-8bc7-fae536dc30b8
dce2e586-096e-4b18-8bc7-fae536dc30b8
Location
Arrowhead Stadium
1 Arrowhead Dr, Kansas City, MO
Phone: (816) 921-3600
1 Arrowhead Dr, Kansas City, MO
Phone: (816) 921-3600
Owner
Attn: Jackson County Sports Authority
Jackson County Sports Authority
1 ARROWHEAD DR, KANSAS CITY, MO 64129
Phone: (816) 920-4962
Email: krutter@chiefs.nfl.com
Jackson County Sports Authority
1 ARROWHEAD DR, KANSAS CITY, MO 64129
Phone: (816) 920-4962
Email: krutter@chiefs.nfl.com
Billing
Attn: Jackson County Sports Authority
Jackson County Sports Authority
1 ARROWHEAD DR, KANSAS CITY, MO 64129
Phone: (816) 920-4962
Email: tidel@chiefs.nfl.com
Jackson County Sports Authority
1 ARROWHEAD DR, KANSAS CITY, MO 64129
Phone: (816) 920-4962
Email: tidel@chiefs.nfl.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | repair the governor remote trip/reset so it works | 7/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | No | No | Replace emergency light battery, it is dead | 7/28/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(c) | No | No | The Maintenance Control Program On-Site documents are not in the machine room. | 7/28/2025 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. | 7/28/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(j) | No | No | did not have a fire extinguisher in the machine room | 7/28/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency lights did not come on, the alarm bell worked, replace the batteries, verify the battery charger is functioning. | 6/7/2022 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate in the machine room is from 2017 | 7/28/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | A Maintenance Control Program (MCP) for each unit shall be provided by the person and/or firm maintaining the equipment and shall be viewable onsite by elevator personnel at all times. | 7/28/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(c)(2) | No | No | A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room. | 7/28/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | Did not have a written record of the maintenance performed on this elevator in the machine room. | 7/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone continues to ring even after answering service answers the phone, the ringing makes two way conversation next to impossible | 11/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | move pit lights from behind the counterweight guard to the enter of the back wall and where the elevator car will not hit them | 7/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | Move pit lights from behind the counterweight guards to the center of the back wall and where the elevator car will not hit them |