Inspection
Inspection Details
Equipment ID
2703
2703
Inspection Date
5/28/2021
5/28/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Craig Loveall
Craig Loveall
Relief Valve Pressure
260
260
Slide
Governor Rope Pull
Door Closing Force
n/a
n/a
External ID
77b96db7-98e0-40b5-9eac-473e3f9772c9
77b96db7-98e0-40b5-9eac-473e3f9772c9
Location
School of Dentistry
650 E 25TH ST, KANSAS CITY, MO
Phone: (816) 235-1363
650 E 25TH ST, KANSAS CITY, MO
Phone: (816) 235-1363
Owner
Attn: Chauncy Kuhl
UMKC- Campus Facilities Mgmt
1011 E 51st St, Kansas City, MO 64110
Phone: (816) 235-1363
Email: kuhlc@umkc.edu
UMKC- Campus Facilities Mgmt
1011 E 51st St, Kansas City, MO 64110
Phone: (816) 235-1363
Email: kuhlc@umkc.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)5 | need to have two working ligh fixtures in the car | |||
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Repair pit light, it did not work. possible burnt out bulb | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | x | Replace the emergency light battery, it is dead | 6/4/2020 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current copy of the state operating certificate in the machine room | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Provide access to the complete MCP in the machine room according to 8.6 | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | bottom landing freight door hoistway access pull chain cover lock is broken and needs to be repaired | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | replace the emergency light battery, it is almost dead | 8/16/2021 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. the one in the room is from 2016 | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.7 Record of Oil Usage | could not find the any of the oil record logs, logs are to be kept in the machine room for 5 years. | |||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display in the machine room is from 2017 | |||
| MO Minimum : Elevators | (A) - Hoistways | (A)5 | Replace missing pull strap on level B hoistway door | |||
| MO Minimum : Elevators | (I) - Pits | (I)1 | Water in the pit, unclogged floor drain in the pit | |||
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Pit light does not work no lightbulb in fixture, replace lightbulb | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Recovery pump in the pit needs to be replaced with a 5 gallon bucket per state memo 6 (8.6.5.5.2) |