When shutting off C/B for car lights to check emergency battery shunt trip breaker shuts down elevator when you turn the C/B for car lights back on. Whoever wired in shunt tip did not do it correctly in must be corrected.
|
9/30/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
NEC 620 When shutting off C/B for car lights to check emergency battery, shunt trip breaker shuts down elevator when you turn the C/B for car lights back on. Whoever wired up Shunt trip did not do it correctly. It must be corrected. 2nd Request.
|
9/30/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Need In Case of Fire signs by each hall call button
|
12/21/1202
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Phone is not working. Line to controller is good.
|
8/31/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working
|
6/30/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
In case of fire use stairs signage needed
|
12/21/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door must be self-locking
|
12/21/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working. Phone?
|
7/17/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door must be self-locking
|
12/21/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working. Line?
|
4/2/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room door must be self-locking
|
12/21/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working. Phone line good. Needs programming from bldg IT department
|