Inspection
Inspection Details
Equipment ID
20946
20946
Inspection Date
7/12/2021
7/12/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Robert Dawes
Robert Dawes
Mechanic Name
Relief Valve Pressure
0
0
Slide
Governor Rope Pull
Door Closing Force
0
0
External ID
33c118eb-da12-4b10-8bfb-bb49834c4c10
33c118eb-da12-4b10-8bfb-bb49834c4c10
Location
Branson Quarters
3245 Falls Pkwy, Branson, MO
Phone: (417) 294-4549
3245 Falls Pkwy, Branson, MO
Phone: (417) 294-4549
Owner
Attn: Steve
Branson Quarters LLC
PO Box 1700, Hollister, MO 65673
Phone: (417) 294-4549
Email: ap@smbzconstruction.com
Branson Quarters LLC
PO Box 1700, Hollister, MO 65673
Phone: (417) 294-4549
Email: ap@smbzconstruction.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | No | No | Repair the light in the car ceiling as two bulbs are required to be burning. | 3/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency alarm buzzer don't work. | 6/10/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in thd machine room. | 3/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | No | No | Replace missing braille plate 2nd. floor | 3/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No current operating certificate displayed. | 3/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | Replace missing braille plate top landing. | 3/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 | No | No | Replace lighting in machine room to provide a minimum of 19 fc at floor level. | 3/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | No | No | Replace or repair car lighting to provide minimum of 5 fc at threshold. | 3/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Remove storage of equipment not related to elevator. | 3/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.7.1.1 | No | No | Remove wood shelf that is not fire rated. | 3/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.11.1 | No | No | No monthly fire service operations log. | 3/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | No on-site documentation of a maintenance control plan accessible for review. (Hydraulic oil log only). | 3/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | No in case of fire signs at landings. | 3/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair in car emergency phone. | 7/12/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices | Yes | Yes | No fire service initiating devices installed. | 7/12/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)9 | No | No | Elevator service keys shall be accessible on-site. | 3/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Debris in pit clean pit. | 3/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | Car top needs to be cleaned excessive debris built up. | 3/20/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | Repair or replace ventilation AC / Heat unit. | 3/20/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room. | 3/20/2023 |