Inspection
Inspection Details
Equipment ID
17945
17945
Inspection Date
6/28/2018
6/28/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Kenneth Gustavson
Kenneth Gustavson
Relief Valve Pressure
Slide
Governor Rope Pull
N/A
N/A
Door Closing Force
19
19
External ID
33543896-8e97-4356-b45a-55e988a411c0
33543896-8e97-4356-b45a-55e988a411c0
Location
Chapel View
4249 MICHIGAN AVE, SAINT LOUIS, MO
4249 MICHIGAN AVE, SAINT LOUIS, MO
Owner
4249 Michigan LLC
4249 MICHIGAN AVE, SAINT LOUIS, MO 63111-1126
4249 MICHIGAN AVE, SAINT LOUIS, MO 63111-1126
Billing
Attn: 4249 Michigan LLC
4249 MICHIGAN AVE, SAINT LOUIS, MO 63111-1126
4249 MICHIGAN AVE, SAINT LOUIS, MO 63111-1126
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Machine room door must be self closing and locking. | 11/14/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.11.2.1.4(e) | No | No | Hoistway access switch does not function at the top floor. | 11/14/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 1/13/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 10/5/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | Permanent electric lighting shall be provided in the machine room and shall be not less than 19 fc at the floor level. Note: The fixtures on the ceiling with extension cords attached to them are not allowed. | 7/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 12/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.14 - Ventilation | 2.14.2.3 | No | No | The interior cover of the cab ventilation fan is missing and shall be replaced. | 7/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | No | No | The code data plate required by A17.1 2005, Section 8.9, shall be provided in plain view, securely attached to each main line disconnect or controller. | 7/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 7/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. | 7/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 7/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.5 Counterweight Runby Data Plate | No | No | A counterweight runby data plate shall be provided in the pit. | 7/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.8.1 Electrical Equipment and Wiring | No | No | The machine room air conditioners must be permanently wired. Note: The extension cord attached to a light fixture hanging over the machine is not allowed. | 7/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | Permanent electric lighting shall be provided in the machine room and shall be not less than 19 fc at the floor level. Note: The fixtures on the ceiling with extension cords attached to them are not allowed. | 7/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.8.1 Electrical Equipment and Wiring | No | No | The machine room air conditioners must be permanently wired. Note: The extension cord attached to a light fixture hanging over the machine is not allowed. | 7/7/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean. Clean the pit. | 3/25/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | The hoistway is in need of a clean down. | 3/25/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 9/18/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Evacuation procedures are missing from the MCP. | 3/25/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | Permanent electric lighting shall be provided in the machine room and shall be not less than 19 fc at the floor level. | 3/25/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power needs to be tested. | 4/2/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.4 Protection of Light Bulbs and Tubes | No | No | Emergency light cover in car is missing. | 3/25/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not being answered and the recording is difficult to hear. | 4/2/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | Emergency light does not work. | 4/2/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency two-way communication device is not functioning. (2nd Notice) This violation must be corrected immediately or the elevator will be red tagged and locked out of service until corrected. | 7/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | Yes | No | Emergency power jewel in hall station is not operational. | 7/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | Yes | No | Emergency power jewel in hall station is not operational. Note: No generator company or maintenance personnel present to test on 7/15/25. | 3/25/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit needs to be cleaned. | 7/16/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | Yes | No | Emergency power jewel is still not repaired. | 7/16/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.5 - Normal terminal stopping device | 8.11.2.2.5 | Yes | No | Final terminal stopping device needs a cover over it. | 7/16/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.8.1 Electrical Equipment and Wiring | No | No | Need outlet in the machine room. | 7/16/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No State operating certificate in the machine room. | 7/16/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.7.1.1 | No | No | Machine room ceiling leaks, it must be properly sealed to keep water and other debris out. | 8/31/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 8.11.2.1.2(bb) | Yes | No | Governor rope has broken lays in a few spots. Must be replaced. | 8/31/2026 |