Inspection
Inspection Details
Equipment ID
14954
14954
Inspection Date
5/21/2021
5/21/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Craig Loveall
Craig Loveall
Relief Valve Pressure
430
430
Slide
Governor Rope Pull
Door Closing Force
10
10
External ID
984a7c54-e55f-4503-8124-13d8d27506c8
984a7c54-e55f-4503-8124-13d8d27506c8
Location
Durwood Soccer Stadium
5100 CHERRY ST, KANSAS CITY, MO
Phone: (816) 235-1363
5100 CHERRY ST, KANSAS CITY, MO
Phone: (816) 235-1363
Owner
Attn: Chauncy Kuhl
UMKC- Campus Facilities Mgmt
1011 E 51st St, Kansas City, MO 64110
Phone: (816) 235-1363
Email: kuhlc@umkc.edu
UMKC- Campus Facilities Mgmt
1011 E 51st St, Kansas City, MO 64110
Phone: (816) 235-1363
Email: kuhlc@umkc.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | replace emergency phone, phone line tested active, the phone in the elevator is dead and needs replaced | 5/29/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current copy of the state operating certificate in the machine room | 6/12/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Post monthly fire service test log in the machine room | 6/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide access to the complete MCP in the machine room according to 8.6 | 6/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine room fire extinguisher inspection tag expired | 6/12/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone did not work, phone line was dead | 8/16/2021 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(c) | No | No | The Maintenance Control Program On-Site documents are not in the machine room. | 6/12/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | the monthly fire service test log is missing | 6/12/2026 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(c)(1) | No | No | the oil record log is missing | 6/12/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display in the machine room is from 2019 | 6/12/2026 |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | Yes | No | the emergency light battery is dead, replace battery | 6/13/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.11 - Plunger and Cylinder | 8.6.5.5 Gland Packings and Seals | No | No | replace the packing on the jack, it is leaking and overfilling the collection bucket in the pit between Maintenance visits | 6/12/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | clean up oil on the pit floor and remove oil soaked rags | 6/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace packing on jack that is leaking significantly | 6/12/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean up oil on pit floor and remove oil soaked rags | 6/12/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | Yes | No | Replace Phase I key switch due to intermittent issues | 6/6/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone. | 8/12/2026 |