Inspection
Inspection Details
Equipment ID
9078
9078
Inspection Date
7/6/2021
7/6/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Gregory Sacks
Gregory Sacks
Mechanic Name
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
6038a798-bcc1-4049-8114-a510ac4115f6
6038a798-bcc1-4049-8114-a510ac4115f6
Location
Terrace Lofts
1300 Convention Plz, St. Louis, MO
Phone: (314) 621-7800
1300 Convention Plz, St. Louis, MO
Phone: (314) 621-7800
Owner
Attn: Terraceloftsrobert LLC & Terraceloft LLC & Terraceloftsrst LLC
Terraceloftsrobert LLC & Terraceloft LLC & Terraceloftsrst LLC
393 N Euclid, ste 300, St. Louis, MO 63108
Phone: (000) 000-0000 Ext: 135
Email: steve@redbrickstl.com
Terraceloftsrobert LLC & Terraceloft LLC & Terraceloftsrst LLC
393 N Euclid, ste 300, St. Louis, MO 63108
Phone: (000) 000-0000 Ext: 135
Email: steve@redbrickstl.com
Billing
Attn: Terrace Lofts LLC
UE Management
7801 Forsyth Blvd, Ste 200, Clayton, MO 63105
Phone: (314) 309-7035 Ext: 135
Email: Laurieb@uemstl.com
UE Management
7801 Forsyth Blvd, Ste 200, Clayton, MO 63105
Phone: (314) 309-7035 Ext: 135
Email: Laurieb@uemstl.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair inoperable emergency phone. | 2/17/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | Yes | No | Machine room wiring shall be enclosed. | 7/6/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | Yes | No | The machine room lighting shall not be less than 19fc at the floor level. | 7/6/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | Yes | No | An ABC type fire extinguisher shall be provided in the elevator machine room. | 7/6/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.1 - Car platform guard | 8.11.2.1.4(a) | Yes | No | Car platform guard shall be 48". | 7/6/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | Yes | No | Provide temperature and humidity control. | 7/6/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.11.2.1.5(b) | Yes | No | Provide counterweight runby signage. Signage shall be 1" stamped, etched, or cast lettering. | 7/6/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 8.11.2.1.2(d) | Yes | No | Seal all machine room penetrations. | 7/6/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 8.11.2.1.4(h) | Yes | No | Seal all hoistway penetrations. | 7/6/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | Yes | No | Provide code compliant pit lighting. | 7/6/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.11.2.1.4(e) | Yes | No | Adjust bottom hoistway access. | 7/6/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 1/16/2023 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 3/1/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Fire extinguisher is still out of date | 3/1/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | The fire extinguisher has no certification tag. | 3/1/2026 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Fire extinguisher does not have a date tag. | 3/1/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/1/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Operating certificate shall be posted in machine room. | 3/1/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be kept clean and dry. Past Water shows at least 2 feet high. | 3/1/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Yes | No | Repair or replace rusty buffer springs. | 3/1/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Yes | No | repair or replace rusty pit channel | 3/1/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Yes | No | repair or replace rusty governor tail sheave | 3/1/2026 |
| A17.1-2016 : Elevators | 3.20 - Governor rope | 8.10.3.2.3(u) | Yes | No | Governor rope has been exposed to water and is rusty. Shall be replaced. 30 days. | 2/26/2026 |
| A17.1-2016 : Elevators | 4.5 - Access to Hoistway | 2.12.7 | No | No | Hoistway Access Keyswitch shall work at top and bottom landings. | |
| A17.1-2016 : Elevators | 3.28 - Counterweight and counterweight buffer | 8.7.2.4 | Yes | No | Counterweight roller guides have been exposed to water and are rusty. Shall be replaced. | 2/26/2026 |