Inspection
Inspection Details
Equipment ID
2854
2854
Inspection Date
7/26/2021
7/26/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Jerry Reasoner
Jerry Reasoner
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
23
23
External ID
20453832-5832-4e9e-85fa-3ce16425a7b1
20453832-5832-4e9e-85fa-3ce16425a7b1
Location
US Bank
415 FRANCIS ST, SAINT JOSEPH, MO
Phone: (816) 233-2000
415 FRANCIS ST, SAINT JOSEPH, MO
Phone: (816) 233-2000
Owner
Attn: Warren Brown
US Bank
3640 S Noland Rd, Ste 200, Independence, MO 64055
Phone: (816) 521-3388
Alt Phone: (816) 332-3874
Email: warren.brown@usbank.com
US Bank
3640 S Noland Rd, Ste 200, Independence, MO 64055
Phone: (816) 521-3388
Alt Phone: (816) 332-3874
Email: warren.brown@usbank.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Car lighting is less than 5 ft candles of illumination. Need to provide adequate lighting inside the elevator. | 3/16/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Need to test firefighters operation monthly and keep written record log inside machine room. | 3/16/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Test and log firefighter operation monthly | 9/20/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Elevator cab lighting is insufficient, less than 5 foot candles of illumination. | 9/20/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Braille plates next to car button #1, and on floor 1 entrance frame need a star on them to designate 1 as the main fire landing. Remove star on LL car button, and floor LL entrance frame. | 9/20/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Remove firefighter call cancel button from car operating panel. Firefighter operation on this elevator was not designed for call cancel feature. | 8/31/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate in the machine room. | 9/20/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door needs to be self-locking | 9/20/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed in machine room | 9/20/2022 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | REPLACE BAD HOIST ROPES | 7/30/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | THE 110VAC BREAKER LABELED ELEVATOR #1 DID NOT REMOVE POWER. WE COULD NOT TEST EMERGENCY LIGHT AND ALARM | |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | REPLACE BAD HOIST ROPES | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | EMERGENCY PHONE NOT WORKING |