Inspection
Inspection Details
Equipment ID
9822
9822
Inspection Date
7/20/2021
7/20/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Rick Brenner
Rick Brenner
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
External ID
b60240a5-a823-4f61-b1b4-f154504271fd
b60240a5-a823-4f61-b1b4-f154504271fd
Location
Edward Jones Dome
901 N Broadway, St. Louis, MO
Phone: (314) 342-5094
901 N Broadway, St. Louis, MO
Phone: (314) 342-5094
Owner
Attn: America's Center
America's Center
701 Convention Plz, St. Louis, MO 63101
Phone: (314) 342-5118
Email: mgruhala@explorestlouis.com
America's Center
701 Convention Plz, St. Louis, MO 63101
Phone: (314) 342-5118
Email: mgruhala@explorestlouis.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Perform unit clean down | 3/31/2026 |
| conversion | conversion | n/a | No | No | Replace upper and lower comb sections with broken tooth, | 3/31/2026 |
| conversion | conversion | n/a | No | No | Replace step with broken tread fin, damage is located at tread riser intersection, | 3/31/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(E) | No | No | Replace upper and lower comb sections with broken tooth. 7.7 | 3/31/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2 | No | No | Replace step with broken thread fin. Damage is located at tread riser intersection. 7.9 | 3/31/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(D) | No | No | Perform unit clean down. 8.6.8.13 | 3/31/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators | 8.1 - Machinery space access, lighting, receptacle, and condition | 8.6.8.14 | No | No | Clean out lower and upper pits. Relamp lower pit. | 3/31/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Perform unit cleandown. | 3/31/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.6 Steps | Yes | No | Replace step with broken fin. Damage is located at tread riser intersection. | 7/15/2021 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | Provide written maintenance control program including wiring diagrams to be kept on site. | 3/31/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.2 Escalator Step-to-Skirt Clearance | Yes | No | Perform step indexing test. | 7/20/2021 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | Maintenance logs need to be updated. | 3/31/2026 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Clean upper and lower pits. | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | Yes | No | Repair demarcation lighting in lower and upper end. | 7/20/2021 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.11.5.2(i) Demarcation lighting | Yes | No | Repair demarcation lighting in the lower and upper end | 4/7/2023 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.13 Escalator Cleaning | No | No | Clean upper and lower pits | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | Maintenance logs to be updated | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | (T)2(H) | No | No | Replace light in lower pit area | |
| A17.1-2016 : Elevators | 7.5 - Lighting | 8.6.11.6.2(i) | No | No | The demarcation light fixtures failed to illuminate and shall be repaired/ replaced. | |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.1.4 Maintenance Records | No | No | MCP shall be kept up to date | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | 3 steps have fins broken, 2 on the nose, one on the tread. Replace as needed |