Inspection
Inspection Details
Equipment ID
17857
17857
Inspection Date
8/3/2018
8/3/2018
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Ronald Edwards
Ronald Edwards
Mechanic Name
Kirk Luttrell
Kirk Luttrell
Relief Valve Pressure
Slide
n/a
n/a
Governor Rope Pull
n/a
n/a
Door Closing Force
24
24
External ID
179fd824-7786-4ada-ab0b-1109f78e5e04
179fd824-7786-4ada-ab0b-1109f78e5e04
Location
Independence Regional Health Center
19600 E 39TH ST S, INDEPENDENCE, MO
19600 E 39TH ST S, INDEPENDENCE, MO
Owner
Center Point Medical Center
19600 E 39TH ST S, INDEPENDENCE, MO 64057-2301
19600 E 39TH ST S, INDEPENDENCE, MO 64057-2301
Billing
Attn: Independence Regional Health Center
19600 E 39TH ST S, INDEPENDENCE, MO 64057-2301
19600 E 39TH ST S, INDEPENDENCE, MO 64057-2301
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | no records on site | 7/10/2025 |
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.7.2.25 | No | No | new mach. no rope gripper | 2/25/2021 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | No | No | couldnt test emg power at time of insp | 2/25/2021 |
| A17.1-2016 : Elevators | 2.16 - Overhead Beam and Fastenings | 8.7.2.9 | No | No | no report from lic. prof. eng. on support for new floor an mach. beams | 7/10/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | No | No | standby power test didnt work properly | 2/25/2021 |
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.7.2.25.1 | No | No | no rope gripper or emg. brake | 2/25/2021 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | No | No | no mcp on site | 7/10/2025 |
| A17.1-2016 : Elevators | 2.16 - Overhead Beam and Fastenings | 8.7.2.9 | No | No | no report on mach.room floor over hoistway by prof. eng. | 6/24/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt. on display | 6/24/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | couldnt test at this time scheduled for april | 2/27/2023 |
| A17.1-2016 : Elevators | 2.16 - Overhead Beam and Fastenings | 8.7.2.9 | No | No | no report on mach. room floor by prof. eng. | 7/10/2025 |
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.7.2.25.1 | Yes | No | emg. brake was not installed as per code | 2/27/2023 |
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.6.4.19.11 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake | Yes | No | unintended motion failed | 2/27/2023 |
| A17.1-2016 : Elevators | 4.1 - Car platform guard | 2.15.9 | No | No | platform guard needs to be 48ins. with emg. brake | 6/12/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt. displayed | 6/24/2024 |