Inspection
Inspection Details
Equipment ID
20131
20131
Inspection Date
7/28/2021
7/28/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Elder
Michael Elder
Mechanic Name
Craig Loveall
Craig Loveall
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
5a2d38cd-3910-4320-8ee3-69f065f344cf
5a2d38cd-3910-4320-8ee3-69f065f344cf
Location
Cass Medical Center
2800 E Rock Haven Rd, Harrisonville, MO
Phone: (816) 380-3474
Alt Phone: (816) 380-3474
Email: fgeasland@cassregional.org
2800 E Rock Haven Rd, Harrisonville, MO
Phone: (816) 380-3474
Alt Phone: (816) 380-3474
Email: fgeasland@cassregional.org
Owner
Attn: Plant Operations
Cass Regional Medical Center
2800 E ROCK HAVEN RD, HARRISONVILLE, MO 64701
Phone: (816) 380-3474 Ext: 4530
Email: fgeasland@cassregional.org
Cass Regional Medical Center
2800 E ROCK HAVEN RD, HARRISONVILLE, MO 64701
Phone: (816) 380-3474 Ext: 4530
Email: fgeasland@cassregional.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | All elevators on Emergency power generator. Could not tested because of Surgeries Scheduled on day of annual test must reschedule EP test. | 7/28/2021 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Standby power not tested. Have to schedule good time for hospital. | 3/7/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self-locking | 9/22/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Car door restrictor broken and needing parts | 9/28/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | oil on pit floor | 4/26/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | couldnt test emg power at time of insp. | 10/2/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | oil on pit floor | 4/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | No | No | emg.power illumination not working | 4/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Telephone not functioning outside line not active. | 12/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency Power Operation could not be witnessed on the date selected for the annual inspection. Must set date for testing the Power Transfer. | 12/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit Floors shall be free of oil and debris. Inverted Piston Oil containers per design shall not be allowed to overflow. | 10/7/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | No | No | illumanation lt didnt work | 10/7/2025 |