Inspection
Inspection Details
Equipment ID
20116
20116
Inspection Date
7/28/2021
7/28/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Elder
Michael Elder
Mechanic Name
Craig Loveall
Craig Loveall
Relief Valve Pressure
540
540
Slide
Governor Rope Pull
Door Closing Force
FDP 25/ RDP 23
FDP 25/ RDP 23
External ID
d2688ba9-8aee-4e92-b815-280983f2cbbf
d2688ba9-8aee-4e92-b815-280983f2cbbf
Location
Cass Medical Center
2800 E Rock Haven Rd, Harrisonville, MO
Phone: (816) 380-3474
Alt Phone: (816) 380-3474
Email: fgeasland@cassregional.org
2800 E Rock Haven Rd, Harrisonville, MO
Phone: (816) 380-3474
Alt Phone: (816) 380-3474
Email: fgeasland@cassregional.org
Owner
Attn: Plant Operations
Cass Regional Medical Center
2800 E ROCK HAVEN RD, HARRISONVILLE, MO 64701
Phone: (816) 380-3474 Ext: 4530
Email: fgeasland@cassregional.org
Cass Regional Medical Center
2800 E ROCK HAVEN RD, HARRISONVILLE, MO 64701
Phone: (816) 380-3474 Ext: 4530
Email: fgeasland@cassregional.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | All elevators on EP Generator. Could not test power transfer because of surgeries scheduled. Must reschedule EP transfer Test. | 7/28/2021 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Standby power not tested | 3/7/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | oil on pit floor | 4/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell not working | 10/2/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | couldnt test emg. power at time of insp | 10/2/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | oil on pit floor | 4/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | No | No | emg power illumination lt. not working | 4/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Telephone not functioning outside line not active. Must Reinspect. | 12/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency Power Operation & Transfer could not be witnessed on the day of the annual inspection. Must set date for testing. Witnessed the Generator Test Log unit was last tested on 7/3/24 | 12/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | No | No | Illumanation lt didnt work | 9/12/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self-locking | 9/12/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm not working. Bad bell. Replace | 9/12/2025 |