Inspection
Inspection Details
Equipment ID
20115
20115
Inspection Date
7/28/2021
7/28/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Elder
Michael Elder
Mechanic Name
Craig Loveall
Craig Loveall
Relief Valve Pressure
580
580
Slide
Governor Rope Pull
Door Closing Force
FDP 25 / RDP 20
FDP 25 / RDP 20
External ID
e81be52c-9da0-4449-9d38-f47f502d2890
e81be52c-9da0-4449-9d38-f47f502d2890
Location
Cass Medical Center
2800 E Rock Haven Rd, Harrisonville, MO
Phone: (816) 380-3474
Alt Phone: (816) 380-3474
Email: fgeasland@cassregional.org
2800 E Rock Haven Rd, Harrisonville, MO
Phone: (816) 380-3474
Alt Phone: (816) 380-3474
Email: fgeasland@cassregional.org
Owner
Attn: Plant Operations
Cass Regional Medical Center
2800 E ROCK HAVEN RD, HARRISONVILLE, MO 64701
Phone: (816) 380-3474 Ext: 4530
Email: fgeasland@cassregional.org
Cass Regional Medical Center
2800 E ROCK HAVEN RD, HARRISONVILLE, MO 64701
Phone: (816) 380-3474 Ext: 4530
Email: fgeasland@cassregional.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | All elevators on EP Generator. Could not test Power Transfer due to surgery schedules. Must Re-reschedule EP Transfer test. | 7/28/2021 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Standby power not tested | 3/7/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | oil on pit floor | 4/26/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | unable to test emg. power at time of insp. | 10/2/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | oil on pit floor | 4/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | No | No | emg power illumination lt not working | 4/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Telephone not functioning. No outside line must Reinspect. | 12/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency Power Operation and Transfer Switch could not ne witnessed on the day selected for the annual inspection. Must re-schedule test. | 12/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | No | No | illumination lt didnt work | 9/12/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | phone wasnt answeredin the allotted time an when it was thy couldt idenify the proper elev. | 3/11/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | No | No | no emg power indicator lt.at designated floor | 9/12/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self-locking | 9/12/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone |