Inspection
Inspection Details
Equipment ID
6983
6983
Inspection Date
7/23/2021
7/23/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
ba4d0e9c-b83f-4b3a-9af0-857bdbc5356b
ba4d0e9c-b83f-4b3a-9af0-857bdbc5356b
Location
Hilton Frontenac
1335 S Lindbergh Blvd, Frontenac, MO
Phone: (314) 993-1100
1335 S Lindbergh Blvd, Frontenac, MO
Phone: (314) 993-1100
Owner
Attn: UNK
Frontenac Property Owner LLc
71 S WACKER DR STE 2130, CHICAGO, IL 60606
Phone: (000) 000-0000
Email: mark.wilson@stlhilton.com
Frontenac Property Owner LLc
71 S WACKER DR STE 2130, CHICAGO, IL 60606
Phone: (000) 000-0000
Email: mark.wilson@stlhilton.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace expired battery in door restrictor control box. | 10/29/2019 |
| conversion | conversion | n/a | No | No | Pit light shall work. | 10/22/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Water from ceiling pipes in machine room leaking onto tank #6. Repair leaks and gutter pipes. | 10/29/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the pit. | 10/29/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Car failed to maintain floor level during 15 minute standing test. - Reinspection Required | 10/29/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Provide 2 working bulbs in emergency lighting in car. | 10/29/2019 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Provide testing of Phase 1 & Phase 2 Fire service. No keys available to test fire service. A set of fire service keys shall be kept on site at all times. | 9/25/2019 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Battery lowering device does not work per code. Where auxiliary power lowering operation is installed or altered, it shall conform to 3.26.10. | 11/9/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work with and without main power, and give proper location. | 8/14/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | MCP is not present in the machine room at this time. | 8/26/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Repair or replace the hoistway door. Exterior skin peeling, hazard at first floor. | 8/26/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Replace missing ceiling tiles in the machine room. | 8/26/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Controller workspace is obstructed by light fixture such that the controller door cannot be fully opened. Take corrective action. | 8/26/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean. Remove excess debris. | 8/26/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | Category 5 testing is due on the overspeed valve or before the next annual inspection. | 8/26/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/25/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Controller workspace is obstructed such that the controller door cannot be opened. Take corrective action | 12/12/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Auxiliary power lowering shall be operational. | 11/7/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Alarm button jams/sticks. Take corrective action as needed. | 6/5/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Replace missing door guide/gib on first floor door. | 6/5/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Note: PM/callback/repair/testing logs incomplete or missing for 2022 - 2024. | 6/5/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service testing must be documented monthly. No documentation for 2022 - 2024 and most of 2025. | 6/5/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 6/5/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean. Remove excess debris. | 6/5/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall give proper location message, Responding Agent could not provide location or elevator number. | |
| A17.1-2016 : Elevators | 1.3 - Operating control devices | 8.11.2.1.1(c) | No | No | Alarm button jams/sticks. 2nd notice | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. | 6/11/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire Service must be tested and properly documented monthly on Log Sheet located in the MCP. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean. Remove excess debris. |