Inspection
Inspection Details
Equipment ID
22474
22474
Inspection Date
7/28/2021
7/28/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Robert Suedkamp
Robert Suedkamp
Relief Valve Pressure
410
410
Slide
Governor Rope Pull
Door Closing Force
16
16
External ID
ec8030fa-8993-40ff-b329-04d672522ca7
ec8030fa-8993-40ff-b329-04d672522ca7
Location
West Pine Lofts, LLC
4050 W Pine Blvd, St. Louis, MO
Phone: (314) 300-4604
4050 W Pine Blvd, St. Louis, MO
Phone: (314) 300-4604
Owner
Attn: West Pine Lofts, LLC
West Pine Lofts, LLC
150 E Broad St, Ste 200, Columbus, OH 43215
Phone: (000) 000-0000
West Pine Lofts, LLC
150 E Broad St, Ste 200, Columbus, OH 43215
Phone: (000) 000-0000
Billing
Attn: West Pine Lofts, LLC
West Pine Lofts, LLC
4050 W Pine Blvd, St. Louis, MO 63108
Phone: (314) 300-4604
Email: dsuarez@peakcampus.com
West Pine Lofts, LLC
4050 W Pine Blvd, St. Louis, MO 63108
Phone: (314) 300-4604
Email: dsuarez@peakcampus.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | In cab emergency telephone shall work. | 10/1/2018 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Rescue plan is missing. (This item is for notification purposes for future violation in 2022) | 1/20/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be displayed in the elevator machine room. | 9/24/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 7/20/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car telephone shall be operational. Note: this was also a violation last year that was not corrected as of 7/20/2023. The phone shall be made operational in 14 days or less or the elevator will be red tagged. | 7/31/2023 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/24/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. | 9/24/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | The machine room temperature shall be kept within the manufacturers recommended range. Note: The air conditioning in the machine room is not working. | 9/24/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 9/24/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | This elevator is equipped with an overspeed valve. Based on the installation date of 2015, a category 5 test will be due in 2025. | 9/24/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/24/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | Fire service testing log shall be documented monthly. | 9/24/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 9/24/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | x | This elevator is equipped with an overspeed valve. Based on the installation date of 2015, a category 5 test will be due in 2025. | 11/20/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.30 - Hydraulic Power Unit | 3.24 | x | The pumping unit belts shall be adjusted so they do not slip under load. | 11/20/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.8 - Top emergency exit | 2.14.1.5 | x | Cartop emergency exit switch has been rendered inoperative (chain is detached from bracket). | 11/20/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | x | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 11/20/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | x | The machine room temperature shall be kept within the manufacturers recommended range. Note: The air conditioning in the machine room is not working. | 11/20/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | x | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. | 11/20/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/20/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | x | Cartop shall be kept free of excess debris/dirt/lint. | 11/20/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | x | Machine room lighting needs to be repaired. One or more bulbs are not working. | 11/20/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump pump shall be provided | x | Sump pump has been rendered inoperative. Repair as needed. | 11/20/2025 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | x | This elevator is equipped with an overspeed valve. Based on the installation date of 2015, a category 5 test is due. | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.30 - Hydraulic Power Unit | 3.24 | x | The pumping unit belts shall be adjusted so they do not slip under load. | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.8 - Top emergency exit | 2.14.1.5 | x | Cartop emergency exit switch has been rendered inoperative (chain is detached from bracket). | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | x | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | x | The machine room temperature shall be kept within the manufacturers recommended range. Note: The air conditioning in the machine room is not working. | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | x | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | x | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | x | Cartop shall be kept free of excess debris/dirt/lint. | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | x | Machine room lighting needs to be repaired. One or more bulbs are not working. | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump pump shall be provided | x | Sump pump has been rendered inoperative. Repair as needed. |