Inspection
Inspection Details
Equipment ID
14968
14968
Inspection Date
7/12/2021
7/12/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Jasen Kennedy
Jasen Kennedy
Relief Valve Pressure
460
460
Slide
Governor Rope Pull
Door Closing Force
13
13
External ID
3c4df86a-51fa-440f-975a-30feff334601
3c4df86a-51fa-440f-975a-30feff334601
Location
Jackson County Family Courts
625 E 26TH ST, KANSAS CITY, MO
Phone: (816) 435-4999
625 E 26TH ST, KANSAS CITY, MO
Phone: (816) 435-4999
Owner
Jackson County Family Courts
625 E 26TH ST, KANSAS CITY, MO 64108-2719
625 E 26TH ST, KANSAS CITY, MO 64108-2719
Billing
Attn: Jackson County Family Courts
625 E 26TH ST, KANSAS CITY, MO 64108-2719
625 E 26TH ST, KANSAS CITY, MO 64108-2719
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | do not store non-elevator related material in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | the alarm bell did not work on battery power | 7/12/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | the emergency phone did not work, no dial tone | 7/12/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | open egg crate ceiling panels, the light tubes shall be guarded | |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)4 | No | No | does not have crosshead data tag | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | No | No | the hydraulic tank is not marked #4 | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | do not store non elevator related material in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | the emergency lights did not come on, the alarm bell worked | 8/17/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency phone did not work | 8/17/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | the pit bucket was overflowing in the pit | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | clean up oil and water mixture on the pit floor | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | elevator has an open egg crate drop ceiling panels, light tubes shall be guarded to prevent breakage | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | emergency lights and bell did not work, replace battery so that the emergency lights and bell work when the 110 volt power is off. | 6/21/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone says that it doesn't have emergency number programmed | 6/21/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | No | No | escape hatch is not secured from opening from inside the elevator | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | adjust the door restrictor, the hook did not catch | 6/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | does not have a crosshead data tag, provide a crosshead data tag | |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | the fire service phase 1 audible signal in the car operating panel did not work | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | the emergency light battery is dead, replace the emergency light battery | 6/5/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone has not been programmed with the phone number to call, program the emergency phone | 6/5/2024 |