Inspection
Inspection Details
Equipment ID
13947
13947
Inspection Date
8/11/2017
8/11/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Unknown Conversion
Unknown Conversion
Mechanic Name
Relief Valve Pressure
Slide
Governor Rope Pull
Door Closing Force
19
19
External ID
Location
University Plaza Apartments
607 N Grand Blvd, St. Louis, MO
Phone: (314) 862-5955
607 N Grand Blvd, St. Louis, MO
Phone: (314) 862-5955
Owner
Kohner Properties
1034 S. Brentwood Blvd, Ste 1300, St. Louis, MO 63117
1034 S. Brentwood Blvd, Ste 1300, St. Louis, MO 63117
Billing
Attn: Kohner Properties
1034 S. Brentwood Blvd, Ste 1300, , MO 63117
1034 S. Brentwood Blvd, Ste 1300, , MO 63117
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | The car top inspection station would not operate properly consistently. The inspection station shall be repaired or replaced to operate as designed. | 6/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | There is no fire extinguisher in the machine room, as required. Provide an ABC type extinguisher of proper size for the room. | 6/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The car top inspection station would not operate properly consistently. The inspection station shall be repaired or replaced to operate as designed. | 6/1/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The elevator light switch cover plate was missing on the day of inspection, replace cover plate for proper operation and safety of maintenance personnel. | 6/1/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Cover access hole for safety keyway with metal instead of plastic. | 6/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Lights and bell not working | 2/8/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Expired | 4/13/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Door restrictor out of adjustment | 2/8/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | No | No | Button not working | 2/8/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Car top dirty | 4/13/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Expired | 4/13/2023 |