Inspection
Inspection Details
Equipment ID
15688
15688
Inspection Date
8/5/2021
8/5/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Nicolas Dominguez
Nicolas Dominguez
Relief Valve Pressure
Slide
0
0
Governor Rope Pull
0
0
Door Closing Force
0
0
External ID
f4ae1e3d-1761-4d24-9ee8-c92ffb0fa2fd
f4ae1e3d-1761-4d24-9ee8-c92ffb0fa2fd
Location
Jackson County Detention Center
1300 CHERRY ST, KANSAS CITY, MO
Phone: (000) 000-0000
Email: jtomlinson@jacksongov.org
1300 CHERRY ST, KANSAS CITY, MO
Phone: (000) 000-0000
Email: jtomlinson@jacksongov.org
Owner
Attn: Brian Gaddie
Jackson County
303 W Walnut St, Independence, MO 64050
Phone: (816) 881-4496
Email: Bgaddie@jacksongov.org
Jackson County
303 W Walnut St, Independence, MO 64050
Phone: (816) 881-4496
Email: Bgaddie@jacksongov.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Main hoisting ropes undersized. Min. 594 actual .590 | 5/20/2019 |
| MO Minimum : Elevators | (A) - Hoistways | (A)7 | No | No | Basement level landing door missing pick up rollers. | 10/29/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)7 | No | No | Gibs on both car and landing doors worn, and loosening. | 10/29/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)2 | No | No | Car stabilizers on cartop worn, causing lateral movement. | 10/29/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | No | No | Landing door gibs badly worn, all floors. | 10/29/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)4 | No | No | Car door gibs badly worn. | 10/29/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide MCP, or location of MCP in machine room. | 10/29/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Provide fire service testing log in machine room, and document monthly testing. | 10/29/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Debris in pit. | 10/21/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean car top. | 10/21/2021 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)7 | Yes | Yes | Both governor adjustment means are missing seals. | 8/5/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | 4th FL landing door interlock missing cover. | 8/5/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 8/30/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | FFS Phase II not working, Phase I recall ok. | 8/13/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Cartop light switch has intermittent problem, and not always works. | 5/22/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | Yes | Repair the emergency lights and bell. | 5/29/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repaired the emergency lights and bell. | 5/22/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | Yes | Repair the emergency lights and bell. | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the pit. | |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Phase II is not working. |