Inspection
Inspection Details
Equipment ID
10679
10679
Inspection Date
8/5/2021
8/5/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Nicolas Dominguez
Nicolas Dominguez
Relief Valve Pressure
Slide
0
0
Governor Rope Pull
0
0
Door Closing Force
0
0
External ID
a004f31d-4550-42ad-8530-e610b380c229
a004f31d-4550-42ad-8530-e610b380c229
Location
Jackson County Detention Center
1300 CHERRY ST, KANSAS CITY, MO
Phone: (000) 000-0000
Email: jtomlinson@jacksongov.org
1300 CHERRY ST, KANSAS CITY, MO
Phone: (000) 000-0000
Email: jtomlinson@jacksongov.org
Owner
Attn: Brian Gaddie
Jackson County
303 W Walnut St, Independence, MO 64050
Phone: (816) 881-4496
Email: Bgaddie@jacksongov.org
Jackson County
303 W Walnut St, Independence, MO 64050
Phone: (816) 881-4496
Email: Bgaddie@jacksongov.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Reinstall existing rope guards on machine. (leaning against wall) | 10/29/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | No | No | Landing door gibs badly worn, all floors. | 10/29/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)4 | No | No | Car door gibs badly worn. | 10/29/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)6 | No | No | Landing door interlock missing cover. FL 8 | 10/29/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm not working. | 5/13/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide MCP, or location of MCP in machine room. | 10/29/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Provide fire service testing log in machine room, and document monthly testing. | 10/29/2020 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)7 | Yes | Yes | One governor adjuster missing seal. | 8/5/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Overhead lighting above machine & controller partially burned out. Only one bulb is working. | 8/30/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 8/30/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Zero counterweight runby in pit. Counterweight making contact with buffer, less than 3" compression. | 5/4/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Comp chain making slight contact with the pit channel during operation. Rule 202.4 | 8/30/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide MCP in machine room. | 8/30/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | Yes | Repair the emergency lights and bell. | 5/29/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency light and bell | 5/22/2026 |