Inspection
Inspection Details
Equipment ID
8882
8882
Inspection Date
7/20/2021
7/20/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Bruce Dorsey
Bruce Dorsey
Relief Valve Pressure
530
530
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
32ae837e-55b4-4584-a5c8-9f424291aadb
32ae837e-55b4-4584-a5c8-9f424291aadb
Location
William Chrisman High School
1223 N NOLAND RD, INDEPENDENCE, MO
Phone: (816) 521-2720
1223 N NOLAND RD, INDEPENDENCE, MO
Phone: (816) 521-2720
Owner
Attn: Geri Frink
Independence School District
201 N Forest Ave, Independence, MO 64055
Phone: (816) 521-5330 Ext: 61007
Email: Geri_frink@isdschools.org
Independence School District
201 N Forest Ave, Independence, MO 64055
Phone: (816) 521-5330 Ext: 61007
Email: Geri_frink@isdschools.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Need to perform and post monthly fire service test log in the elevator machine room | 11/25/2019 | ||
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | do not store non-elevator related material in the machine room | 11/25/2019 | ||
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | provide working phone line to the elevator controller, the phone line that is there is dead. | 7/27/2020 | |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | n/a | Provide a ABC fire extinguisher convenient to the access door | 2/23/2021 | ||
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | backup battery failed to operate | 2/23/2021 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | The Maintenance Control Program (MCP) On-Site documents are not in the machine room. | 1/3/2022 | ||
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | The firefighters service test log is not being filled out monthly. | 1/3/2022 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.7 Record of Oil Usage | could not find an oil record log in the machine room | 1/3/2022 | ||
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | label the controller, tank, disconnect, car top, and pit Elevator #2 | 1/3/2022 | ||
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | the next overspeed valve test will be due in 2022 | 1/3/2022 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | could not find Maintenance Control Program (MCP) documents in the machine room | 10/27/2025 | ||
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | did not find monthly fire service test log in the machine room | 10/27/2025 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.1 Not less than two lamps | Only one emergency light bulb worked, replace burnt out emergency light bulb | |||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | x | Door restrictor missing parts, repair door restrictor so it works |