Inspection
Inspection Details
Equipment ID
20477
20477
Inspection Date
7/26/2021
7/26/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Douglas Miller
Douglas Miller
Relief Valve Pressure
Slide
1"
1"
Governor Rope Pull
25/220
25/220
Door Closing Force
22
22
External ID
a9b1f05a-a43b-4cf4-9e67-62fe88d706c4
a9b1f05a-a43b-4cf4-9e67-62fe88d706c4
Location
Clayton High School
1 Mark Twain Cir, Clayton, MO
Phone: (314) 943-0094
1 Mark Twain Cir, Clayton, MO
Phone: (314) 943-0094
Owner
Attn: Jim Brennell
Clayton School District
2 MARK TWAIN CIR, CLAYTON, MO 63105
Phone: (000) 000-0000
Email: deborahsperruzza@claytonschools.net
Clayton School District
2 MARK TWAIN CIR, CLAYTON, MO 63105
Phone: (000) 000-0000
Email: deborahsperruzza@claytonschools.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | No | No | Emergency light is not operational. | 11/20/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be posted in the elevator machine room. | 1/28/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/27/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.4 Means for Manual Release | No | No | Provide means to release the brake from outside the hoistway. | 8/27/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency phone shall be operational. Speaker is not working/ cannot hear other person. | 9/8/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The in car emergency lights are not working. | 9/8/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication works, but the volume is extremely low; increase volume. 14-day re-inspection extension granted. | 10/17/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | Yes | The phone line is now dead. Red Tag Issued. The emergency phone shall be operational and code compliant. | 10/23/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.4 Means for Manual Release | Yes | No | Provide means to release brake from outside of hoistway. | 7/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 | Yes | No | Safety retainers missing on hoistway doors (fire tabs). | 7/21/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.4 Means for Manual Release | Yes | No | A means of picking the brake from outside the hoistway must be provided. (2nd notice) |