Inspection
Inspection Details
Equipment ID
11056
11056
Inspection Date
7/26/2021
7/26/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Vincent Daus
Vincent Daus
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
e2092fa3-6079-46f8-b21a-885d2e94e9c3
e2092fa3-6079-46f8-b21a-885d2e94e9c3
Location
Hidden Lake Care Center
11750 HIDDEN LAKE DR, SAINT LOUIS, MO
Phone: (314) 355-5153
11750 HIDDEN LAKE DR, SAINT LOUIS, MO
Phone: (314) 355-5153
Owner
Attn: Hidden Lake Care Center
Hidden Lake Care Center
11750 HIDDEN LAKE DR, SAINT LOUIS, MO 63138
Phone: (000) 000-0000
Email: modea@estatesofhiddenlake.com
Hidden Lake Care Center
11750 HIDDEN LAKE DR, SAINT LOUIS, MO 63138
Phone: (000) 000-0000
Email: modea@estatesofhiddenlake.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate. | 11/21/2018 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational with 24/7 support. | 11/4/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a copy of the current state operating certificate. | 3/15/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | The pit shall be kept clean and dry. Remove water and clean the pit. | 7/26/2021 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | The cab lighting guards are missing and shall be replaced. Lighting shall be guarded or covered. | 7/26/2021 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | The machine room lighting shall be operational. | 7/26/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 7/26/2021 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 3/13/2024 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 3/13/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | Evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 3/15/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. | 3/15/2024 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | The overspeed valve is not sealed and has been previously cited that a category 5 test is needed. A category 5 test shall be performed within 90 days. | 2/27/2024 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | The machine room lights shall be operational. | 3/15/2024 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 101.5a Lighting | No | No | The machine room lights shall be guarded. | 3/15/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | The in-car stop switch shall not be rendered inoperative on phase one fire service until the car is in motion. | 2/27/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 2/27/2024 |
| A17.1-1996 : Elevators | 2.14 - Code data plate | 215 | No | No | The code data plate required by A17.1 2016, 2016 8.9 shall be provided in plain view, securely attached to each main line disconnect or controller. | 3/15/2024 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | The data on the MCP shall be filled out as required by A17.1 2016 8.6.1.4.1(a)(3). | 3/15/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 2/27/2024 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | Yes | No | A category 5 test of the overspeed valve shall be performed within 90 days. | 3/15/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/10/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 207.8 | Yes | No | Emergency power must be tested annually. | |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Fire extinguisher is out dated. |