Inspection
Inspection Details
Equipment ID
15715
15715
Inspection Date
7/25/2018
7/25/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Richard DuFrenne
Richard DuFrenne
Relief Valve Pressure
510
510
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
e985c32e-0829-4844-ac4c-35768fce4c68
e985c32e-0829-4844-ac4c-35768fce4c68
Location
Convention Center
600 N 6TH ST, SAINT LOUIS, MO
600 N 6TH ST, SAINT LOUIS, MO
Owner
Metro Accounts Payable
707 N 1ST ST, SAINT LOUIS, MO 63102-2505
707 N 1ST ST, SAINT LOUIS, MO 63102-2505
Billing
Attn: Metro Accounts Payable
PO BOX 1349, SAINT LOUIS, MO 63188-1349
PO BOX 1349, SAINT LOUIS, MO 63188-1349
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency light not working. | 12/18/2019 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x | Emergency alarm bell not working. | 12/18/2019 | |
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | Cab ventilation not working. | 12/1/2020 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display updated certificate in machine room. | 12/1/2020 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Need a maintenance control program on site | 1/13/2022 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | Oil line fitting going into tank leaking oil onto floor needs repair | 1/13/2022 | ||
MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | Machine room can not be used for storage of non elevator equipment | 12/7/2021 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.35 - Supply Line and Shutoff Valve | 3.19 | Replace leaking victaulic fitting on hydraulic line in the machine room. Fitting is on the bottom side of the shut off valve | 12/7/2021 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | Phone in the elevator cab does not work. Repair or replace | 2/1/2022 | |
A17.1-2016 : Elevators | 1.14 - Ventilation | 2.14.2.3 | x | Elevator cab ventilation fan does not work on auxiliary power (battery power) needs repaired. Re-inspection required | 10/4/2024 | |
A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | x | Elevator cab door restrictor does not work, needs repaired. Re-inspection required | 10/4/2024 | |
A17.1-2016 : Elevators | 4.2 - Hoistway doors | 8.6.4.13 Door Systems | x | Safety retainers are missing on top & bottom hoistway doors, need to install safety retainers. Re-inspection required | 10/4/2024 |