Inspection
Inspection Details
Equipment ID
17737
17737
Inspection Date
7/23/2018
7/23/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Richard DuFrenne
Richard DuFrenne
Relief Valve Pressure
550
550
Slide
Governor Rope Pull
Door Closing Force
29
29
External ID
5b0752e4-515b-4c4a-b285-b8a74b83ad6c
5b0752e4-515b-4c4a-b285-b8a74b83ad6c
Location
Forest Park Station
250 DE BALIVIERE AVE, SAINT LOUIS, MO
250 DE BALIVIERE AVE, SAINT LOUIS, MO
Owner
Metro Accounts Payable
707 N 1ST ST, SAINT LOUIS, MO 63102-2505
707 N 1ST ST, SAINT LOUIS, MO 63102-2505
Billing
Attn: Metro Accounts Payable
PO BOX 1349, SAINT LOUIS, MO 63188-1349
PO BOX 1349, SAINT LOUIS, MO 63188-1349
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.1a | No | No | Per NEC, repair disconnect and replace 4x4 box cover. | 11/4/2020 |
| A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | No | No | Disconnect is rusting out due to water damage. | 11/4/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated certificate in machine room. | 11/4/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certificate in machine room | 11/4/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need maintenance control program on site posted on controller | 11/4/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Need fire service log posted in machine room to be tested monthly | 11/4/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Water damage on electric disconnects in machine room | 11/4/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(b)(2) Hydraulic elevators Placed out of Service | Yes | Yes | Severe water damage. | 7/12/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit lighting is not working, needs to be repaired | 11/7/2023 |
| A17.1-1996 : Elevators | 1.14 - Ventilation | 204.3c | Yes | No | Elevator cab ventilation fan does not work on auxiliary power (battery backup), needs repaired. Re-inspection required | 10/10/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator cab phone does not work, needs repaired. Re-inspection required | 11/4/2025 |