Inspection
Inspection Details
Equipment ID
2598
2598
Inspection Date
8/12/2021
8/12/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Joseph Jensen
Joseph Jensen
Mechanic Name
Thomas Nash
Thomas Nash
Relief Valve Pressure
540
540
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
475a185f-6f21-4a37-8151-7c010330d5eb
475a185f-6f21-4a37-8151-7c010330d5eb
Location
Track & Soccer Complex
Providence & Stadium, Columbia, MO
Phone: (573) 882-6463
Providence & Stadium, Columbia, MO
Phone: (573) 882-6463
Owner
Attn: Debra Anderson - Facility Operations
UMC-General Services
180 General Services Bldg, Columbia, MO 65201
Phone: (573) 884-5300
Email: mumuopselevatorin1@missouri.edu
UMC-General Services
180 General Services Bldg, Columbia, MO 65201
Phone: (573) 884-5300
Email: mumuopselevatorin1@missouri.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Insufficient machine room lighting | 11/13/2019 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Telephone not dialing to a monitored location | 5/13/2020 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | No emergency light/alarm | 5/13/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State operating certificate in machine room | 5/27/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Fire service hall key switch bezzel faded and unreadable | 5/27/2020 |
| A17.1-1996 : Elevators | 2.3 - Lighting and receptacles | 1001.2(b)(3) Inspection code | No | No | Provide a 110V AC GFI outlet in machine room | 9/8/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Replace missing fire service Phase 1 instructions at main landing | 9/26/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Replace missing fire service Phase 2 instructions in car | 9/26/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | G) 8.6.1.6.7 Replace missing "Do not use elevator in case of fire" Signage on 2nd landing. | 9/26/2022 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Reinstall cover, rear wall of pit, to cover water fountain plumbing. | 9/26/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | No | No | Need to install code data plate on controller. | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need to add Fire service Phase I instructions at main landing | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need to replace missing Phase II instructions inside elevator cab | 12/7/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)13 | No | No | Need to install cover over exposed water pipes in back wall of hoistway. Repair leaks in water pipes that belong to the drinking fountains outside hoistway in back | 12/7/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Elevator pit has water in it, pits should be kept clean & dry | 12/7/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need to install code data plate on controller. | 7/30/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Need Fire service Phase I instructions on main landing | 7/30/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Replace missing Phase I instructions inside elevator cab | 7/30/2024 |
| MO Minimum : Elevators | (A) - Hoistways | (A)1 | No | No | Install cover over exposed water pipes in back wall of hoistway. Repair leaks in water pipes that belong to the drinking fountains outside hoistway in back. | 7/30/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Elevator pit has water in it, pit should be kept clean & dry | 7/30/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Check and repair programming of this phone for proper operation and passenger safety. Re-inspection required | 8/19/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need to replace Fire service Phase I instructions at Main Landing | 8/19/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need to replace missing Phase I instructions inside the elevator cab | 8/19/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide current year tested fire extinguisher in the elevator machine room. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Seal all holes in machine room. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Relamp machine room lights as needed. |